Slant/Fin Gas Hot Water User Manual

Slant/Fin Equipment

Advertising
background image

HOT WATER/GAS

Modular Boilers

APPLICATION GUIDE

Publication No. CG-10-HWG

Printed in the U.S.A. 1212

www.slantfin.com

Guidelines for the design, purchase and installation of Slant/Fin Caravan gas-fired, hot water modular boiler systems.

®

CONTENTS

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

Ratings and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,3

Recommended Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

Optional factory supply and return headers . . . . . . . . . . . . . .5

Boiler room design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

Boiler room air supply requirements . . . . . . . . . . . . . . . . . . . .6

Typical layouts for gas-fired systems . . . . . . . . . . . . . . . . . . .7

Venting a gas-fired system . . . . . . . . . . . . . . . . . . . . . . . . . .8,9

Gas piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10,11

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11,12

SC- control bill of materials . . . . . . . . . . . . . . . . . . . . . . . . . .12

Field wiring at modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

SC-3 system wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

SC-3 ladder wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

SC-9 space heating wiring . . . . . . . . . . . . . . . . . . . . . . . . . .16

SC-9 space heating ladder wiring . . . . . . . . . . . . . . . . . . . . .17

SC-9 space and domestic hot water wiring . . . . . . . . . . . . .18

SC-9 space and domestic hot water ladder wiring . . . . . . . .19

Caravan warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21,22

Request for Caravan rating plate . . . . . . . . . . . . . . . . . . .23,24

CODES AND STANDARDS

All Caravan installations must comply to local codes or, in the
absence of local codes, to the National Fuel Gas Code, ANSI,
Z223.1-latest edition.

In addition where required by the authority having jurisdiction, the
installation must conform to American Society of Mechanical
Engineers Safety Codes for controls and safety devices for

automatically fired boilers, No. CSD-1. The installation must also
conform to the additional requirements of Slant/Fin Instruction Book
publication no. GG-100-40 latest edition.

All electrical wiring is to be done in accordance with the National
Electrical Code ANSI/NFPA No. 70-latest edition and all local electri-
cal codes. The unit must be electrically grounded if an external

power source is used.

In Canada, the installation must be in accordance with standards
CGA B149.1 and B149.2, installation codes for gas burning
appliances and equipment and/or local codes. All electrical

connections are to be made in accordance with Standard C.S.A.
C22.1 Canadian Electrical Code Part 1 and/or local codes.

Many state and local codes require intermittent ignition devices for
gas boilers. Please specify if necessary.

INTRODUCTION OF FRESH WATER

Introduction of excessive amounts of fresh water into a system can
cause scaling and leave deposits in the boiler and the surrounding
pipes. This will lead to inefficient boiler operation and breakdown.
Fresh water will enter the system as a result of hidden leaks such
as may occur in underground piping. Relief valves should be piped

to a location that shows visible signs of relief.

Process applications that use fresh water, require the use of heat
exchangers. Any process application that results in introduction of

fresh water into a boiler can cause scaling with deposits forming in
the boiler and surrounding piping. This will damage the boiler.
Introduction of fresh water from leaks will cause similar damage.

In some areas it may be necessary to use a feed water treatment to
control the corrosive makeup of the feed water. Check with the local
authority, to determine if the feed water will need a conditioning

treatment before being supplied to the boiler.

LOCAL CODE APPROVALS

New York City:

GGT and GGHT Caravan Modules - MEA 283-93-E Vol. II
Slant/Fin vent damper NYS approval No. 8859

Pennsylvania:

Caravan boilers are approved in Pennsylvania by PA Cert. 174-BT-S