This control can be programmed as follows:

1. Outdoor reset: The supply water temperature is

automatically adjusted up or down based on outdoor

temperature. The control automatically controls the

number of modules required to maintain required supply

water temperature.

2. Setpoint temperature: The control can be programmed

to maintain a set supply water temperature. The control

automatically controls the number of modules activated to

maintain the setpoint temperature.

SC-9 Control

The SC-9 control allows up to 9 stages of operation for space

heating, domestic water or combination, in a Caravan system.

Generally each stage controls 1 module. However, it is possible to

have more than one module activated with each stage.

Standard programmable features include: system activation or
de-activation based on outdoor temperature; minimum target sup-

ply water temperature; adjustable design target supply water tem-

perature; adjustable delay between stages; adjustable

outdoor and indoor design temperatures; delay to allow

combustion air damper to open; ability to provide equal run time

rotation of boiler modules; fixed lead of a module when Caravan

system activates; first on/last off or first on/first off for modules;

control of primary circulator and periodic exercising of primary cir-

culator when system is inactive.

The view menu on the control includes error messages, actual

outdoor air temperature, actual supply water temperature,

target water temperature, running time for each stage and the dif-

ference between supply water and return water

temperatures.

The SC-9 can be programmed as follows:

1. Outdoor reset: The supply water temperature is

automatically increased as outdoor temperature

decreases and decreased as outdoor temperature

increases. The control activates only the number of stages

required to maintain the required supply water

temperature.

2. Setpoint temperature: The control maintains a set supply

water temperature. The control activates only the number

of stages required to maintain the setpoint temperature.

Setpoint temperature may be used for a Caravan system

that is dedicated for use as volume water heating.

3. Domestic hot water: The domestic hot water controls

override the SC-9 control for only those modules used to

heat the domestic hot water. The modules for domestic

hot water are isolated from space heating system until

demand for domestic hot water is satisfied. The modules

not used for domestic hot water heating remain under

control of SC-9 control.

Slant/Fin offers domestic hot water control packages and

external tankless heaters as options for use with the SC-9

control.

BILL OF MATERIALS FOR SC SERIES CONTROLLERS

Other Options include:

• Immersion well for supply water sensor: to be installed in control header supplied with Caravan

• High Limit (manual reset) and Immersion Well: to be installed in control header supplied with Caravan

• Low Water Cut-Off (manual reset): to be installed in modular boiler headers above modules cast iron heat exchanger

• Domestic Hot Water Control Packages: components include EMV valve; setpoint aquastat L6006A with immersion well. This is to

be used with external heat exchanger such as Caravan BP series brazed plate heat exchangers.

Circulators, switches, wiring and other relays are provided by contractor.

Material List for SC-3

• SC-3 modular boiler control (part# 435-084)

• 1 Outdoor sensor (part # 339-070)

• 1 Universal sensor to be used as supply water sensor

(part # 339-071)

• 1 Plastic tie strap

Material List for SC-9

• 1 SC-9 modular boiler control (part # 435-085)

• 1 Outdoor sensor (part # 339-070)

• 2 Universal sensors (part # 339-071)

-

1 to be used as supply water sensor

-

1 can be used as return water sensor

• 2 Plastic tie straps