Slant/Fin Sentry Series User Manual

Automatic vent damper, Warning, For galaxy, sentinel and sentry series boilers

Advertising
background image

For Galaxy, Sentinel
and Sentry Series Boilers

The installation must conform to the requirements of

the authority having jurisdiction or, in the absence of

such requirements, to the National Fuel Gas Code,

ANSI Z223.1-latest edition.

In addition, where required by the authority having

jurisdiction, the installation must conform to American

Society of Mechanical Engineers Safety Code for

Controls and Safety Devices for Automatically Fired

Boilers, No. CSD-1.

THIS MANUAL MUST BE LEFT WITH OWNER AND

SHOULD BE HUNG ON OR ADJACENT TO THE

BOILER FOR REFERENCE.

The vent damper shipped with your boiler may be a different model than illustrated above.

WARNING

By failing to follow the WARNING instructions listed below, a hazardous condition

such as explosion, carbon monoxide poisoning, fire or all of these could result.

• This device is design certified by C.S.A. for use only on

specific Slant/Fin Corporation gas boiler models. These

boilers must also be equipped with a plate or rating plate

which states that the boiler must* (may*) be used with a

Slant/Fin Corp. automatic vent damper device and indicates

the proper vent damper model or part number (See Table 1).

*

Boilers under 300,000 Btu/hr. input

MUST use a vent damper.

Note: GG-75 HES (Constant circulation),

MAY use a vent

damper.

Boilers with 300,000 Btu/hr. input or greater equipped with IID

(intermittent pilot ignition)

MAY use a vent damper.

Boilers with 300,000 Btu/hr. input equipped with continuous

pilot and VR8300A gas valve MAY use a vent damper.

This device must be installed and inspected annually by a quali-

fied installer in accordance with the Slant/Fin vent damper

installation instructions, Slant/Fin boiler installation instructions

and the vent damper manufacturer's installation instructions

included with this damper. If improperly installed, a hazardous

condition such as explosion or carbon monoxide poisoning could

result. If installed improperly, all vent damper and boiler war-

ranties shall be voided.

Use of this device on boilers other than those indicated above is
not permitted.

CAUTION: When servicing controls all wires must be labeled
prior to disconnection. Wiring errors can cause improper and

dangerous operation.

This device must be installed on the outlet end of the draft hood

of the boiler as close to the draft hood as practicable, and with-

out modification of the draft hood (see figures 3 through 7).

The inlet size of the vent damper must be the same nominal

trade size as the outlet of the draft hood. See Table 1 for the

boiler models and their corresponding vent damper models.

The device must be located in a venting system or section of a

venting system so that it serves only the single appliance for

which it is installed.

Clearances of not less than 6 inches (152 mm) must be main-

tained from combustible materials, with provisions for access.

If the boiler will not fire, DO NOT jump any of the safety controls

(the vent damper circuit is part of the safety control circuit).

Check page 12 of this manual for troubleshooting guide.

Part No. 41-1676. Printed in U.S.A. 112

Publication No. VD-40, Rev. V

INSTALLATION INSTRUCTIONS AND TROUBLESHOOTING GUIDE

AUTOMATIC VENT DAMPER

READ AND SAVE THESE INSTRUCTIONS

FOR REFERENCE.