Warning – Slant/Fin Sentry Series User Manual

Page 3

Advertising
background image

III. After Installation

1. Operate system through two complete cycles to check for

opening and closing in proper sequence, and proper burner
operation.

Damper must be in open position when boiler

main burners are operating.

2. Perform installation checks as required by ANSI specification

Z21.66. See manufacturer’s vent damper instructions.

3. Replace the front cover of the boiler. (Galaxy models only.)
4. Check the troubleshooting section if problems arise with the

installation.

For more information, see Slant/Fin boiler installation manual GG-
40 for Galaxy, S-40 for Sentry, SE-40 for Sentinel, and the vent
damper manufacturer's booklet shipped with the vent damper.

VENT DAMPER SUITABILITY

Check the rating plate attached to the boiler for proper vent damper
part number to use on the boiler.

WARNING - IMPORTANT

Damper circuit is designed to be controlled by low

voltage controls. DO NOT use line voltage operating con-

trols to interrupt supply voltage to the L8148E and L8124E

aquastats or system transformer on steam system.

CAUTION

Label all wires prior to disconnection when servicing control.

Wiring errors can cause improper and dangerous operation.

“Verify proper operation after servicing”

VENT DAMPER MODEL NUMBER

In Table 1, the proper Slant/Fin Corp. vent damper model numbers are shown adjacent to the specific Slant/Fin Corp. boilers
with which these vent dampers may be used.

WARNING

THIS DEVICE CANNOT BE USED WITH BOILERS WITH 300,000 BTU/HR. INPUT OR GREATER EQUIPPED WITH CONTINU-

OUS PILOT (see note). OTHER VENT DAMPERS OR DEVICES WITH SIMILAR PURPOSE ARE NOT PERMITTED.

Vent Size

Use Slant/Fin Vent

For Slant/Fin Boiler Model No.†

Inches

Damper Part No.

S-34, S-60, SE-70

4

41-2704#

GG-75H, GXH-105, GXHA-100, GXHA-120, S-90, SE-105, SE-140

5

41-2705#

GG-100H, GG-125H, GG-150H, GG-175H, GXH-125, GXHA-160, S-120, SX-150, SE-175

6

41-2706#

GG-200H, GG-225H, GXH-150, GXH-170, GXH-190, GXH-210, GXH-230,

GXHA-200, GXH-250, GXH-275, S-150, SX-180, SX-210, SE-210, SE-245

7

41-2707#

GX-225, GX-250,GG-250H, GG-275H, GG-300, GG-325, GXH-300

8

41-2708#

GG-350, GG-350H, GG-375, GXH-300H

9

41-2709

GG-375H, GG-399H

10

41-2710#

Table 1.

NOTE: BOILERS WITH 300,000 BTU/HR. EQUIPPED WITH HONEYWELL VR 8300A GAS VALVE MAY USE A VENT DAMPER.

† May have suffix “E”, “D”, “P”, “PZ”, etc.

# May be any 3 digits.

Table 2.

DIMENSIONS

Figure 1.

Figure 2.

* May be plugged with plug provided, ONLY if boiler is equipped with an inter-

mittent ignition pilot. Note on Honeywell vent dampers there is only the 7/8

dia. hole and no knockout. For more information on specific vent dampers

see manufacturer’s manual included.

Vent

Size

4"

5"

6"

7"

8"

9"

10"

A

9

5

8

"

10

5

8

"

11

5

8

"

12

5

8

"

13

5

8

"

14

5

8

"

15

5

8

"

Figure 3.

Vertical Installation

Figure 4.

Horizontal or Sloping Installation

Advertising
This manual is related to the following products: