Slant/Fin Gas Hot Water User Manual

Page 9

Advertising
background image

9

Figure 9. Connector rise

Figure 10. Suggested venting system constructions

Connector Rise: Connector rise is the length of the pipe connecting the
top of the draft hood to the system breeching above. The diameter of this

pipe varies depending upon BTU input, chimney height and the length of
the connector. Fig.9 (Dim. “B”) shows the location of this pipe in a typical

application. Table 2a depicts the proper diameter (Dim. “C”) of the connec-
tor rise depending upon its total length (top of the draft hoods to the

breeching above).

Based on single row of modules with no elbows.

NOTE:

For conditions other than those shown, consult factory, or National Fuel

Gas Code NFPA 54.

NOTE:

“E” dimensions (from table 2), when designing breeching dia. is the

same as chimney dia.

Table 2A.

Vent Connector Diameters (20 ft. chimney “F” dim)

Model

Flue Outlet Size

Connector Rise “B”

“A”

3' High

2' High

1' High

“C”

“C”

“C”

GG300ES

8”

8”

10”

10”

GG350HES

9”

9”

10”

12”

GG375HES

10”

10”

10”

12”

GG399HES

10”

10”

12”

12”