Gas Main Sizing
To determine the correct pipe diameter for the gas main serving a specific Caravan

system, proceed as follows:

a. Follow the building plans, find total length of straight pipe between supply from gas

meter and boiler gas header.

b. Using data in Table 4, calculate equivalent linear length of screw pipe fittings used in

fabrications of main. Add this to figure from step (a) to obtain equivalent total length.

c. Find Caravan gas consumption in cubic feet per hour from Table 3 in hot water

systems.

d. Multiply the system total hourly gas consumption by flow correction value from

Table 5.

e. Locate system’s total equivalent pipe length in right column of Table 6.

f.

Move vertically to the system’s corrected flow rate calculated in step (c). If this value

falls between two of those listed, select larger value.

g. From this point move horizontally to the left column and read suggested pipe

diameter for gas main.

GGT-600E

600

GGHT-700E

700

GGHT-750E

750

GGHT-800E

798

GGT-900E

900

GGHT-1050E

1050

GGHT-1125E

1125

GGHT-1200E

1197

GGT-1200E

1200

GGHT-1400E

1400

GGHT-1500E

1500

GGT-1500E

1500

GGHT-1600E

1596

GGHT-1750E

1750

GGHT-1875E

1875

GGHT-2000E

1995

GGHT-2100E

2100

GGHT-2250E

2250

GGHT-2400E

2394

GGHT-2450E

2450

GGHT-2625E

2625

GGHT-2800E

2793

GGHT-2800AE

2800

GGHT-3000E

3000

GGHT-3150E

3150

GGHT-3200E

3192

GGHT-3375E

3375

GGHT-3500E

3500

GGHT-3600E

3591

GGHT-3750E

3750

GGHT-4000E

3990

1/2

0.84

0.52

0.41

0.031

2.50

1.12

1.25

1.66

3/4

1.17

0.73

0.57

0.044

3.50

1.84

1.75

2.33

1

1.57

0.98

0.77

0.057

4.68

2.11

2.34

3.11

1-1/4

2.19

1.37

1.07

0.082

6.54

2.94

3.27

4.35

1-1/2

2.63

1.64

1.29

0.098

7.84

3.52

3.92

5.21

2

3.55

2.23

1.74

1.320

10.60

4.77

5.30

7.05

3

5.72

3.59

2.81

2.130

17.08

7.69

8.84

11.40

Model No.

Gas

Consumption In CFH

Table 3: Gas consumption rate

hot water boilers only

Table 4: Equivalent linear length in feet of standard iron pipe fittings for natural gas

Figure 11. Typical gas supply line installation

Pipe

Size

Inches

Standard

Medium

Sweep

Long

Sweep

Gate

Globe

Angle

Return

Bend

Side

Outlet

Tee

Elbow

Valve

GAS PIPING

This section contains sizing and construction recommendations

for fuel supply piping to Caravan gas-fired modular boiler

systems. Gas-fired equipment must conform not only to codes of

local regulatory agencies, but also to additional specifications that

may be imposed by the utility or gas supplier. Therefore, the

following information should be considered only as a guideline.

Figure 11 illustrates a typical gas supply line installation. It

consists of a main between the utility’s meter box and the boiler

system, a main shut-off valve sediment trap, gas header pipe and

drip legs on individual boilers.

Individual gas lines to individual boiler modules should be

3

4

"

diameter. Size of gas main and header pipes depends on volume

of gas required and acceptable pressure drop between meter and

modules’ gas regulator valves. Minimum pressure required at each

valve is 5 inches of water column for natural gas and 11 inches for

propane gas, measured while all boilers and other gas-fired

equipment on the same meter are firing. Small variations in gas

flow can be compensated for by adjusting gas regulator valves.

However, final pressure of gas header must vary no more than

+ 0.3 in. of water column.