PROCEDURE

Engine Generator Set only

The engine control module (ECM) is manufactured

by Deep Sea Electronics. Model 30 is used on

this engine generator set. See picture below. Ad-

ditional information on the DSE 30 is on pages 4

through 7.

Manual Operation

Press and release the red Stop/Reset button. Then

press and release the green Start Engine button.

The engine generator will crank and start automati-

cally. If the engine fails to start correct the problem

before proceeding.

With the engine running smoothly, check the no load

voltage and frequency at wire #  and # 4 (L2 and

L6 in the ASCO ATS) on the generator terminal block

in the ATS. The voltage should be 240 volts plus or

minus nominal. The frequency should be between

6.5 to 62 hertz (Hz). The voltage should also be

checked between the hot terminals (L2 and L6) and

the neutral to be certain of a balanced voltage output

and a solid neutral connection. The voltage should

be about on half of the line to line voltage.

** NOTICE **

If for any reason during the check out procedures

the voltage and frequency are not correct, press the

Stop/Reset button and correct the trouble before

proceeding.

After verifying the voltage and frequency are correct,

press the Stop/Reset button. This will shut off the

engine immediately.

Transfer Switch & Engine Generator

Automatic (remote) Operation

This procedure checks the electrical operation of

the automatic transfer switch. If the actual operation

does not follow this procedure, consult the trou-

blshooting section in the transfer switch manual.

. Turn on the preferred source (utility) circuit

breaker. The utility source acceptable light should

now come on as well as the transfer switch on utility

light. If these lights fail to come on recheck your

incoming power to insure you have 240 volts nomi-

nal. If not, troubleshoot your utility source before

continuing.

******************

***** WARNING *****

******************

PERSONAL INJURY HAZARD - Install front cover

in transfer switch before operation. An electrical sys-

tem fault could cause a flash and severe personal

injury.

2. Press and release the Auto button on the en-

gine control module (ECM). The auto mode icon will

appear on the screen. The unit is now ready to be

operated from the Automatic Transfer Switch.

3. Turn on the altenate source (generator) curcuit

breaker.

4. Press and hold the

Push to Test button until

the generator (alternate source) acceptable light

comes on and stays on. Then release the button.

This will start up your generator set.

This light indicates that the generator is running and

the output voltage and frequency are within accept-

able limits. Under normal conditions this light should

come on in 5 to 0 seconds. If the light does not

come on and stay on a malfunction has occurred.

Either the unit didn’t start or the voltage or frequency

is incorrect. Correct the problem before continuing.