075-00

4

60706-2

5. About 5 seconds after the generator (alter-

nate source) acceptable light comes on, the auto-

matic transfer switch should transfer the load from

the utility to the generator. At that time the

Transfer

Switch on generator light should come on.

6. The generator will stay connected to the load

for about 5 minutes at which time the transfer switch

will transfer the load back to the utility. At the time it

transfers back to utility the Transfer Switch on Utility

light should come on and the Transfer Switch on

generator light should go out. To bypass this five

minute time delay you can press and release the

Push to Test button again at any time.

7. After the load retransfer to the utility, the gen-

erator will continue to run for about  minute (without

a load) and then shut down. The Generator ac-

ceptable light will go off indicating the generator set

has shut down. This completes the functional test

of the transfer switch and the generator set. If you

want to leave the generator in the Automatic Start

mode you can leave the engine control module in

the auto mode. If you have additional work to do or

don’t want to leave the engine generator set in the

automatic position start mode press and release the

stop/reset button In the off mode the engine genera-

tor set will not start or run.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to

automatically exercise the generator for 20 minutes

once every 4 days.

In order to set and test the exercise circuit the

engine control module must be set in the auto

mode.

SETTING THE EXERCISER CIRCUIT

Press and release the

Automatic Generator Exer-

ciser button. After about 8 seconds the exerciser

light flashes 4 times to indicate that the exerciser

circuit has been set. The number of flashes indi-

cates the number of days until the next exercise

period. This 20 minute period will occur at approxi-

mately the same time of the day the button was

pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off. After about 8 seconds the exerciser light

flashes fourteen times to indicate that the exerciser

circuit has be re-enabled.

******************

***** WARNING *****

******************

WITH A TOTAL POWER FAILURE (UTILITY

POWER FAILS AND THE GENERATOR FAILS TO

START AND RUN) THE EXERCISER MUST BE

RESET AFTER THE POWER IS RESTORED.

CLEARING AN “ERROR” CODE

An error codes occurs on the ASCO control board if

the generator set fails to start or there is some other

malfunction. BOTH Transfer Switch lights will be

blinking together. The Automatic Generator Exer-

ciser light will be blinking a number of times then

pause. This number gives the error code reason

from page 8 of the ASCO 65 owner’s manual. To

clear this code press and release the Push to Test

button once. Then troubleshoot the problem accord-

ing to the ASCO 65 owner’s manual.

This completes your installation and unit testing.

ALWAYS leave the system in automatic mode unless

servicing the unit. For automatic operation, the auto

mode icon must be lite on the engine control module

display.

DSE 3110 ENGINE CONTROL

PROTECTIONS

When an alarm is present, the Common alarm LED

if configured will illuminate.

The LCD display will

show an icon to indicate the failure.

WARNINGS

Warnings are non-critical alarm conditions and do

not affect the operation of the generator system,

they serve to draw the operators attention to an un-

desireable condition. Warning alarms are self-reset-

ting when the fault condition is removed. The icon

will appear steady in the display.

SHUTDOWNS

Shutdowns are critical alarm conditions that stop the

engine and draw the operator’s attention to an un-

desirable condition. Shutdown alarms are latching.

The fault must be removed and the STOP/RESET

button pressed to reset the module. The icon will

appear flashing in the display.