DSE 3110 CONTROL

STOP/RESET (Red Button) This button places the module into its “Stop/

Reset” mode. This will clear any alarm conditions for which the triggering

criteria have been removed. If the engine is running and the module is in

Stop mode, the module will automatically instruct the changeover device to

unload the generator. (Close generator becomes inactive (if used)). The fuel

supply de-energizes and the engine comes to a standstill. Should a remote

start signal be present while operating in this mode, a remote start WILL NOT

occur.

AUTO (White Button) This button places the module into its “Automatic”

mode. This mode allows the module to control the function of the generator

automatically. The module will monitor the remote start input and once a start

request is made, the set will be automatically started and placed on load.

Upon removal of the starting signal, the module will automatically transfer the

load from the generator and shut the set down observing the stop delay timer

and cooling timer as necessary. The module will then wait the next start event.

START (Green button)

Pressing this button in auto mode will start the engine and run off load.

Pressing this button in Stop/Reset mode will turn on the CAN engine ECU

(when correctly configured and fitted to a compatible engine ECU).

PAGE

Pressing this button scrolls the display to show the various instruments.