075-00

60706-208

ferred source) light stays on.

3. To bypass the time delay or cancel the test,

press and release the

Push to Test button again.

4. The generator set stops and the

Generator

acceptacle light goes off.

WITH Load Transfer

. Press and hold the

Push to Test button until

the generator (alternate source) acceptable light

comes on and stays on. Then release the button.

This will start up your generator set.

This light indicates that the generator is running and

the output voltage and frequency are within accept-

able limits. Under normal conditions this light should

come on in 5 to 0 seconds. If the light does not

come on and stay on a malfunction has occurred.

Either the unit didn’t start or the voltage or frequency

is incorrect. Correct the problem before continuing.

2. About 5 seconds after the generator (alter-

nate source) acceptable light comes on, the auto-

matic transfer switch should transfer the load from

the utility to the generator. At that time the

Transfer

Switch on generator light should come on.

3. The generator will stay connected to the load

for about 5 minutes at which time the transfer switch

will transfer the load back to the utility. At the time it

transfers back to utility the Transfer Switch on Utility

light should come on and the Transfer Switch on

generator light should go out. To bypass this five

minute time delay you can press and release the

Push to Test button again at any time.

4. After the load retransfers to the utility, the gen-

erator will continue to run for about  minute (without

a load) and then shut down. The generator accept-

able light will go off indicating the generator set has

shut down.

This completes the functional test of the transfer

switch and the generator set. If you want to leave

the generator in the automatic start mode you can

leave the left hand toggle switch on the generator in

the ON position. If you have additional work to do

or don’t want to leave the engine generator set in

the automatic position start mode move the toggle

switch to the OFF position. In the OFF postion the

alarm light will come on and the generator set will

not start or run.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to

automatically exercise the generator for 20 minutes

once every 4 days.

In order to set and test the exercise circuit the

left hand toggle switch on the generator control

panel must be in the ON position.

SETTING THE EXERCISER CIRCUIT

Press and release the

Automatic Generator Exer-

ciser button. After about 8 seconds the exerciser

light flashes 4 times to indicate that the exerciser

circuit has been set. The number of flashes indi-

cates the number of days until the next exercise

period. This 20 minute period will occur at approxi-

mately the same time of the day the button was

pressed.

DISABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off.

ENABLING THE EXERCISER CIRCUIT

Press and hold the

Automatic Generator Exerciser

button until the light goes off, the light flashes then

goes off. After about 8 seconds the exerciser light

flashes fourteen times to indicate that the exerciser

circuit has be re-enabled.

******************

***** WARNING *****

******************

WITH A TOTAL POWER FAILURE (UTILITY

POWER FAILS AND THE GENERATOR FAILS TO

START AND RUN) THE EXERCISER MUST BE

RESET AFTER THE POWER IS RESTORED.

CLEARING AN “ERROR” CODE

An error codes occurs on the ASCO control board if

the generator set fails to start or there is some other

malfunction. BOTH Transfer Switch lights will be

blinking together. The Automatic Generator Exer-

ciser light will be blinking a number of times then

pause. This number gives the error code reason

from page 8 of the ASCO 65 owner’s manual. To

clear this code press and release the

Push to Test

button once. Then troubleshoot the problem accord-

ing to the ASCO 65 owner’s manual.

This completes your installation and unit testing.

ALWAYS leave the system in automatic mode unless

servicing the unit. For automatic operation, the left

hand toggle switch on the generator control panel

must be left in the “ON” position.