Preventive maintenance – Winco ULPSS12H4W/E User Manual

Page 16

Advertising
background image

075-00

6

60706-208

PREVENTIVE

MAINTENANCE

Reasonable care in preventive maintenance will

insure high reliability and a long life for the generator

set and Automatic Transfer Switch.

*****************

***** WARNING *****

*****************

When performing any type of maintenance on this

equipment make sure the selector switch on the

generator set is in the off position. If you are work-

ing in the Automatic Transfer Switch, confirm with a

reliable meter that all power has been disconnected.

AUTOMATIC TRANSFER SWITCH

Clean and inspect the switch once a year. de-ener-

gize all power sources, both line and generator set,

then brush and vacuum away any excessive dust

or dirty accumulation. You can at this time with the

contactor de-energized remove the contactor covers

and check the contacts. Make sure contacts are

clean and not burned or pitted.

ENGINE GENERATOR SET

Service the engine in accordance with the engine

manufacturers manual provided with your new

equipment. Routinely remove debris and dirt from

around the inside generator enclosure. Insure that

the air intakes are free from leaves and other debris

at all times.

Clean and inspect battery terminals a least twice a

year. Check the battery water level at least twice a

year also.

Other than keeping the generator set clean and

free of debris there is no other routine or preventa-

tive maintenance required, as long as the generator

is run biweekly to keep it dry and in good working

order.

COLD WEATHER OPERATION

Extreme cold weather operation requires special

considerations. Higher CCA batteries are required

for cold weather starting, 650 CCA or larger are rec-

ommended. In addition you should consider install-

ing an oil heater kit and a battery warmer for reliable

starting during cold weather.