DC ELECTRICAL

INTERCONNECTION

**** CAUTION ****

Never run the AC and DC wiring in the same con-

duit.

ASCO 165 UL SWITCH

Your DC connection points in the ASCO 65 UL ATS

are on the terminal block in the upper right hand

corner of the ATS panel. The terminal block (TB7) is

numbered  through 9. These terminals will accept

# 22 - # 4 AWG stranded wire. It is recommended

that you use # 6 AWG for distances up to 200 feet.

You need to run four (4) wires from the generator set

to the transfer switch.

WIRE #

PURPOSE

RECOMMEND

COLOR

# 5

Battery Positive

Black

# 1

Battery Negative

White

# 24

Fuel Solenoid

Red

# 22

Start

Orange

These wire colors are a recommendation only. The

wires terminate on TB7 as follows:

WIRE #

COLOR

TB7 TERMINAL

# 5

Black

# 3

# 1

White

# 2

# 24

Red

# 4

# 22

Orange

# 7

Jumpers will need to be installed as follows:

WIRE #

COLOR

TB7 TERMINAL

# 5

Black

# 3 & # 5

# 5

Black

# 5 & # 8

The following is an optional way to interconnect the

Generator and the Transfer Switch. the wires termi-

nate on TB7 terminal as follows:

WIRE #

COLOR

TB7 TERMINAL

# 1

White

# 2

# 24

Red

# 4

# 22

Orange

# 7

The following leads are wire-nutted together:

WIRE #

COLOR

FROM

# 5

Black

Generator

# 5

Black

TB7 # 3

# 5

Black

TB7 # 5

#5

Black

TB7 # 8