***** WARNING *****

******************

PERSONAL INJURY HAZARD - Install front cover

in transfer switch before operation. An electrical sys-

tem fault could cause a flash and severe personal

injury.

2. Turn on the preferred source (utility) circuit

breaker. The

UTILITY acceptable light should now

come on as well as the

TRANSFER SWITCH on

utility light. If these lights fail to come on, recheck

your incoming power to insure you have 240 volts

nominal. If not, troubleshoot your utility source be-

fore continuing.

3. Turn on the alternate source (generator) circuit

breaker.

There are two ways to test your transfer switch

operation: WITHOUT a load transfer or WITH a

load transfer.

WITHOUT load transfer (normal exercise)

. Press and release the

Push to Test button.

The generator set should start immediately. In about

5 seconds the

GENERATOR acceptable light

comes on and stays on.

2. The generator set runs for 20 minutes. The

Transfer Switch does not transfer the load to the

generator set. The

TRANSFER SWITCH on utility

light stays on.

3. To bypass the time delay or cancel the test,

press and release the

Push to Test button again.

4. The generator set stops and the

GENERATOR

acceptacle light goes off.

WITH Load Transfer

. Press and hold the

Push to Test button until

the

GENERATOR acceptable light comes on and

stays on. Then release the button. This will start up

your generator set.

This light indicates that the generator is running and

the output voltage and frequency are within accept-

able limits. Under normal conditions this light should

come on in 5 to 0 seconds. If the light does not

come on and stay on, a malfunction has occurred.

Either the unit didn’t start or the voltage or frequency

is incorrect. Correct the problem before continuing.

2. About 5 seconds after the

GENERATOR

acceptable light comes on, the automatic transfer

switch should transfer the load from the utility to the

generator. At that time the

TRANSFER SWITCH on

generator light should come on.

3. The generator will stay connected to the load

for about 5 minutes at which time the transfer switch

will transfer the load back to the utility. At the time

it transfers back to utility the

TRANSFER SWITCH

on UTILITY light should come on and the TRANS-

FER SWITCH on generator light should go out. To

bypass this five minute time delay you can press and

release the

Push to Test button again at any time.

4. After the load retransfers to the utility, the gen-

erator will continue to run for about  minute (without

a load) and then shut down. The

GENERATOR

acceptable light will go off indicating the generator

set has shut down.

This completes the functional test of the transfer

switch and the generator set. If you want to leave

the generator in the automatic start mode, you can

leave the left hand toggle switch on the generator in

the

ON position. If you have additional work to do

or don’t want to leave the engine generator set in

the automatic position start mode, move the toggle

switch to the

OFF position. In the OFF postion the

alarm light will come on and the generator set will

not start or run.

GENERATOR EXERCISER CIRCUIT

The automatic generator exerciser is configured to

automatically exercise the generator for 20 minutes

once every 4 days.