Figure 4-38. pre-alarms configuration -41 – Winco DGC-2020 User Manual
Page 111

Figure 4-38. Pre-Alarms Configuration
A
High Fuel Level: Enable or Disable, threshold is adjustable from 0 to 150% in 1 % increments.
B
Low Battery Voltage: Enable or Disable, threshold is adjustable from 6 to 12 Vdc (12 Vdc battery) or 12
to 24 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation delay is adjustable from 1 to 10 s in 1 s
increments.
C
Weak Battery Voltage: Enable or Disable, threshold is adjustable from 4 to 8 Vdc (12 Vdc battery) or 8
to 16 Vdc (24 Vdc battery) in 0.1 Vdc increments. Activation time delay is adjustable from 1 to 10 s in 1 s
increments.
D
Battery Overvoltage: Enable or Disable, threshold is adjustable from 12 to 32 Vdc in 0.1 increments.
E
Maintenance Interval: Enable or Disable, threshold is adjustable from 0 to 5,000 h in 1 h increments.