secondary base speed is 1,800 rpm. The Accelerator Position setting

C

is expressed as a percentage and

tells the Volvo Penta ECU where to set the engine speed (trim) relative to the base speed. The range of
the setting is the base speed

120 rpm. A setting of 0% will cause the engine to run at 120 rpm below the

base speed, a setting of 50% will cause the engine to run at the base speed, and a setting of 100% will
cause the engine to run at 120 rpm above the base speed. The Accelerator Position setting is linear with
a gain of 2.4 rpm/percentage. This setting is not saved in nonvolatile memory and defaults back to 50%
after DGC-2020 operating power is cycled.
If the engine is configured as MTU MDEC, the configuration of the following settings is necessary:

 MDEC Module Type

D

 Speed Demand Switch

E

 Engine

RPM

F

If the engine is configured as MTU ADEC, the configuration of the following settings is necessary:

 Speed Demand Switch

E

- Specifies speed demand source for the MTU engine ECU.

 Engine

RPM

F

- Requested engine RPM when speed demand source is analog CAN for an MTU ECU.

 Overspeed

Test

G

- Temporarily drives an MTU ECU into overspeed for testing overspeed.

 Governor Param Switch Over

H

- Specifies which governor parameters an MTU ECU should use.

 Trip

Reset

I

- Resets trip information such as trip fuel used, trip hours, trip idle time, etc.

 Int Oil Prime

J

- Causes an MTU ECU engine to perform an internal lubrication cycle.

If the engine is configured as MTU ECU7, the configuration of the following settings is necessary:

 Speed Demand Switch

E

- Specifies speed demand source for the MTU engine ECU.

 Engine

RPM

F

- Requested engine RPM when speed demand source is analog CAN for an MTU ECU.

 Overspeed

Test

G

- Temporarily drives an MTU ECU into overspeed for testing overspeed.

 Speed

Up

K

- Increases speed of the MTU ECU.

 Speed

Down

L

- Decreases speed of the MTU ECU.

 Speed Demand Limit

M

- Turns the speed demand limit on or off.

 Increased

Idle

N

- Sets the MTU ECU idle.

 Trip

Reset

I

- Resets trip information such as trip fuel used, trip hours, trip idle time, etc.

 Int Oil Prime

J

- Causes an MTU ECU engine to perform an internal lubrication cycle.

 Engine Start Prime

O

- Turns the engine start prime on or off.

 Fan

Override

P

- Turns the fan override on or off.

 Mode

Switch

Q

- Turns the mode switch on or off.

 Governor Param Switch Over

H

- Specifies which governor parameters an MTU ECU should use.

 Governor Param Set Select

R

- Sets the governor parameter set select.

 CAN Rating Switch 1 & 2

S

- Turns the CAN rating switch 1 & 2 on or off.

 Cylinder Cutout Disable 1 & 2

T

- Turns the cylinder cutout disable 1 & 2 on or off.

The Volvo Penta ECU configuration is applicable only to the EDC3 and EMS2 models of Volvo Penta
engine controllers.