3.5 VIEWING THE EVENT LOG

Event log 1/50

Oil Pressure Low
Shutdown
12 Sep 2007, 08:25:46



The 7000 series modules maintains a log of the last 50 shutdown alarms (7200 series
logs 30 shutdown alarms) to enable the operator or engineer to view the past alarms
history.
The event log only includes shutdown and electrical trip alarms logged;
The event log does not contain Warning alarms.


Once the log is full, any subsequent shutdown alarms will overwrite the oldest entry in the log.
Hence, the log will always contain the most recent shutdown alarms.
The module logs the alarm, along with the date and time of the event in the format shown in this example.

To view the event log, repeatedly press the next page button

until the LCD screen displays the Event log.

Press down

to view the next most recent shutdown alarm:

Continuing to press down

cycles through the past alarms after which the display shows the most recent

alarm and the cycle begins again.

To exit the event log and return to viewing the instruments, press the next page

button.



3.6 USER CONFIGURABLE INDICATORS

These LEDs can be configured by the user to indicate any one of 100+
different functions
based around the following:-

Indications - Monitoring of a digital input and indicating associated

functioning user’s equipment - Such as Battery Charger On or Louver’s
Open, etc
.

WARNINGS and SHUTDOWNS - Specific indication of a particular

warning or shutdown condition, backed up by LCD indication - Such as
Low Oil Pressure Shutdown, Low Coolant level, etc.

Status Indications - Indication of specific functions or sequences

derived from the modules operating state - Such as Safety On, Pre-
heating, Panel Locked, Generator Available, etc.





If All warnings are latched
is configured, the event
log will capture warning
alarms. For more details
consult the 7xxx series
configuration software
manual.

User configurable LEDs

Number of present alarms. This is event 1 of a
total of 50 logged events.