DSE Model 7000 Series Quick Start Guide

18

Part No. 057-101 7000 Series Quick Start Guide ISSUE 1 14/04/2009 JR

4.3.3 ENGINE RUNNING


In manual mode, the load is not transferred to the generator unless a ‘loading request’ is made.
A loading request can come from a number of sources.

Pressing the transfer to generator

button

Mains supply out of limits (DSE7220/DSE7320 only)

Activation of an auxiliary input that has been configured to remote start on load

Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.

NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents

excessive wear on the engine.


Once the load has been transferred to the generator, it will not be automatically transferred back to the mains
supply. To manually transfer the load back to the mains either:

Press the transfer to mains

button (DSE7220/DSE7320 only)

Press the Open Generator button (DSE7210/DSE7310 only)

Press the auto mode

button to return to automatic mode.

4.3.4 STOPPING SEQUENCE


In manual mode the set will continue to run until either :

The stop button

is pressed – The set will immediately stop

The auto button

is pressed. The set will observe all auto mode start requests and stopping timers

before beginning the Auto mode stopping sequence.