SECTION 3 TESTING & SERVICE

3---1

PREVENTIVE MAINTENANCE

For high reliability and long life for the ATS:

Operate the switch at least once a month. Perform this

4–step Electrical Operation Test (test with load transfer).

Transfer Switch Test

1.

Press and hold the door-mounted

Transfer Test button

until the engine starts and runs. This should happen

within 15 seconds.

2.

The transfer switch will operate to the Emergency

position. If the

Transfer To Emergency Delay is used,

the transfer will occur after a time delay (up to 5

minutes). For immediate transfer press

Bypass

Time Delay button.

3.

The Transfer Switch will operate back to the Normal

position after the

Retransfer To Normal Delay (up to

30 minutes). For immediate retransfer press

Bypass Time Delay button.

4.

Unloaded Running (Engine Cooldown) Delay allows

engine to run unloaded for 5 minutes.

Checklist for Yearly Inspection

Hazardous voltage capable of causing shock,

burns, or death is used in this switch.

Deenergize both Normal & Emergency power

sources before performing inspections!

S

Clean the enclosure. De–energize all sources,

then brush and vacuum away any excessive dust

accumulation. Remove moisture with a clean cloth.

S

Check the transfer switch contacts. De-energize

all sources, then remove the transfer switch barriers

and check contact condition. The non–replaceable

main contacts are designed to last the life of the

transfer switch. Reinstall the barriers carefully.

S

Maintain transfer switch lubrication. Under

normal operating conditions no further lubricating

is required. Renew factory lubrication if the switch

is subjected to severe dust or abnormal operating

conditions or if TS coil is replaced. Order lubricant

kit 75–100.

S

Check all cable connections & retighten them.

Torque to values shown on transfer switch label.

Replacement parts. When ordering parts provide the

Serial and Catalog Nos. from the transfer switch

nameplate. Contact ASI. In the US call

1–800–800–ASCO (2726)).

DISCONNECTING THE CONTROLLER

The harness disconnect plugs are furnished for repair

purposes only and should not have to be unplugged.

If the controller must be isolated, follow these steps

carefully.

Disconnecting the Plugs

1. Observe the position of the transfer switch.

a. If the transfer switch is in the Normal position,

place standby engine starting control in the off

position. Then open the emergency source circuit

breaker.

b. If the transfer switch is in the Emergency position,

open the normal source circuit breaker. Place the

engine starting control in the test or run position.

2. Separate the quick disconnect plugs by squeezing

the latches. Do not pull on the harness wires.

3. Label, remove, and tape the signal wires connected

to the engine start terminals on the transfer switch:

TB1 and TB3, or TB1 and TB2.

Reconnecting the Plugs

1. Observe the position of the transfer switch.

a. If the transfer switch is in the Normal position, be

sure that the standby engine starting control is

still in the off position. The emergency source

circuit breaker still should be open.

b. If the transfer switch is in the Emergency position,

normal source circuit breaker still should be open.

2. Reconnect the signal wires connected to the

appropriate engine start terminals on the transfer

switch. See Section 1, Engine Starting Contacts.

3. The harness plugs and sockets are keyed.

Carefully align the plugs with the sockets

and press straight in until both latches click.

4. Restore the opposite source as follows:

a. If the transfer switch is in the Normal position,

place the standby engine starting control in the

automatic

position. Then close the emergency

source circuit breaker.

b. If the transfer switch is in the Emergency position,

close the normal source circuit breaker. The load

will be automatically retransferred to the normal

source after the Retransfer to Normal Delay. For

immediate retransfer, press Bypass Time Delay

button. Place the engine starting control in the

automatic

position.