289c1 – Winco ASCO 300 J Design 600 Amp User Manual

Page 5

Advertising
background image

SECTION 1

INSTALLATION

1---1

Series 300 Automatic Transfer Switches are factory

wired and tested. Installation requires skid removal

then securing the enclosure to the supporting
foundation.

Remove the Shipping Skid

Open the front door and remove the four lag screws (2

in front, 2 in rear) securing enclosure to the wood skid.

Supporting Foundation

The supporting foundation for the enclosure must be

level and straight. Refer to the applicable enclosure
outline drawing included with the Series 300 for all

mounting details including door opening space.

If bottom cable entry is used, the foundation must be
prepared so that the conduit stubs are located

correctly. Refer to the enclosure outline drawing for

specified area and location. Provide cable bending
space and clearance to live metal parts. When a

concrete floor is poured, use interlocking conduit

spacer caps or a wood or metal template to maintain
proper conduit alignment.

Mounting

Refer to the applicable enclosure outline drawing

furnished with this switch and mount the Series 300

according to details and instructions shown on diagram.

Line Connections

Refer to the Wiring Diagram provided with your Series

300 ATS. All wiring must be made in accordance with

the National Electrical Code and local codes.

It is unnecessary to remove pole covers from the

transfer switch. If you do remove them, reinstall them

carefully.

De–energize the conductors before making any

line or auxiliary circuitry connections. Be sure

that Normal and Emergency line connections

are in proper phase rotation. Place engine

generator starting control in the OFF position.

Make sure engine generator is not in operation.

Testing Power Conductors

Do not connect the power conductors to the ASCO
Series 300 transfer switch until they are tested.

Installing power cables in conduit, cable troughs and

ceiling-suspended hangers often requires considerable
force. The pulling of cables can damage insulation and

stretch or break the conductor’s strands. For this

reason, after the cables are pulled into position, and
before they are connected, they should be tested to

verify that they are not defective or have been

damaged during installation.

NOTICE

Protect the automatic transfer switch from

construction grit and metal chips to prevent

malfunction or shortened life of the ATS.

Connecting Power Conductors

After the power cables have been tested, connect them

to the appropriate terminal lugs on the transfer switch

as shown on the wiring diagram provided with this

Series 300. Make sure the lugs provided are suitable
for use with the cables being installed. Standard

terminal lugs are solderless screw type and will accept

the wire sizes listed on the drawings provided with the
Series 300. Be careful when stripping insulation from

the cables; avoid nicking or ringing the conductor.

Remove surface oxides from cables by cleaning with a
wire brush. When aluminum cable is used, apply joint

compound to conductors. Tighten cable lugs to the

torque specified on rating label.

Controller Ground

A grounding wire must be connected to the controller’s
lower left mounting stud. Because the controller is

mounted on the enclosure door, a conductive strap

must be used between the enclosure and the door.
This connection provides proper grounding which does

not rely upon the door hinges.

Harnesses

The transfer switch is connected to the left side of the

controller by a plug–in harness (two plugs).

Advertising