12. TROUBLESHOOTING

Problem Description

Probable Root Cause

Suggested Action

* LCD does not show input voltage value

* AC input failure alarm active
(1 beep / 4s) however AC input source is OK

Input power cord is not connected

Check input power cord connection.

Input power cord is connected into UPS
outlet.

Check input power cord connection.

UPS cannot be powered on even AC input is
OK.
Beep alarm is active (1 beep/s) & LCD shows:

EPO function is active.

Re-establish emergency power off
switch and set UPS in normal mode.

UPS cannot be powered on even AC input is
OK.

ON push button is not been selected
properly

Push ON button during 2 seconds or
longer

1 beep / s alarm is active and LCD shows:

Input Line and Neutral are swapped

Rotate UPS plug at wall socket to allow

correct line-neutral connection. This
suggestion is only valid for Schuko
power plug type.

1 beep / s alarm is active and LCD shows:

Internal or external batteries are not
properly connected

Check battery connection.

* Code 27

* Active:

* Continuous beep

Very high voltage at batteries or
charger failure

Batteries and charger must be
inspected by qualified personnel

* Code 28

* Active:

* Continuous beep

Very low voltage at batteries or charger
failure

Batteries and charger must be
inspected by qualified personnel

* Intermittent:

+

* 2 beeps per second.

UPS overloaded

Disconnect devices from UPS outlets

until solving overload

* Intermittent:

+

* 2 beeps per second.
* By-Pass activated

UPS overloaded. UPS has changed to
BYPASS mode to avoid internal
damage.

Disconnect devices from UPS outlets
until solving overload

After repetitive small overloads, UPS

has changed to BYPASS mode.

Disconnect devices from UPS outlets

until solving overload. Then power off
UPS and re-star again.

* Code 43

* Active:

* Continuous beep

UPS has been automatically powered
off because overload.

Disconnect devices from UPS outlets
until solving overload. Then power ON.

* Active:

on LCD.

* Continuous beep

UPS has been automatically powered

off because short circuit detected at
output.

Check short circuit problem in devices

connected to UPS

* Any of following codes indicated on LCD:
1, 2, 3, 4, 11, 12, 13 o 41
* Continuous beep

Internal Ups failure detected. UPS
working in any of following modes:
1. UPS output powered in BYPASS
mode
2. UPS outlets powered off

Call service support

Very short backup time

Batteries can be discharged because
recent use..

Let UPS recharge batteries during 6
hours before check backup time again.

Battery can be degraded because long

lifetime.

Batteries must be replaced by new

batteries.