OPTIONAL KIT FOR EXTERNAL BATTERIES PACKS

There is a connector optional kit available for OPTIMA & OPTIMA-F series that allows connection of external battery packs to the UPS.
This optional kit can be get as option to be connected in UPS rear panel. This kit offers a DC connector for the rear panel and attached

cable to be connected to internal batteries. In that way internal batteries will be available to be connected to external batteries by DC
connector.

INSTRUCTIONS TO CONNECT EXTERNAL BATTERIES

If UPS already has DC connector installed for External Batteries (EXBATT) follow instructions of this section. If not, install connection kit

according to its manual.

IMPORTANT: Every UPS model has its own DC connector kit with different size and color. This avoids to connect the wrong EXBATT to
your UPS. User must be sure about the kind of EXBATT to be connected to UPS. In case of doubts we recommend to revise product label
and instructions of this manual or ask to XMART distributor.

IMPORTANT: All OPTIMA-HB models come with a firmware protection that limits maximum runtime up to 5 minutes when load connected
to UPS is above 80% of maximum UPS capacity. When connected load is below 80%, UPS will provide the runtime batteries can offer until
reaching low battery level.


UPS

BATTERY
VOLTAGE


UPS

BATTERY
VOLTAGE

UPS

BATTERY
VOLTAGE


UPS

BATTERY
VOLTAGE

OPTIMA 1K

36 VDC

OPTIMA 1K-HB

24 VDC

OPTIMA 1KF

24 VDC

OPTIMA 1KF-CN 24 VDC

OPTIMA 1.5K

36 VDC

-

-

-

-

-

-

OPTIMA 2K

72 VDC

OPTIMA 2K-HB

48 VDC

OPTIMA 2KF

48 VDC

OPTIMA 2KF-CN 48 VDC

OPTIMA 3K

72 VDC

OPTIMA 3K-HB

72 VDC

OPTIMA 3KF

72 VDC

OPTIMA 3KF-CN 72 VDC


1) Place EXBATT close to the UPS
2) We recommend to measure DC voltage on both EXBATT and UPS before making any connections. Input breaker on EXBATT must be in
ON position before measuring DC voltage. Verify both voltages are similar according to above tables.
3) Turn OFF input breaker in all EXBATT to be connected. Connect UPS to first EXBATT using EXBATT cable included in EXBATT box.

4) Connect second EXBATT to first EXBATT in similar way.
5) After connecting all EXBATT, Turn ON all input breakers on EXBATT.


COMUNICATION PORTS

Models (F) and (F-CN) come with USB port inserted in intelligent slot. If a different communication port is required as RS232, LAN Card,
etc, you must remove USB port to connect new port.
Models OPTIMA & OPTIMA-HB already include RS232+USB on rear panel. Intelligent slot is only required for connecting LAN card, Relay
card, etc.