Step 2 — rig and locate the unit, A caution, Step 3 — mount compressor – Carrier 38AQ034 User Manual

Page 2: Step 4 — complete connections, Caution

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Allow sufficient space for airflow clearance, wiring,

refrigerant piping and servicing unit. See Fig. 1.

Locate unit so that condenser airflow is unrestrieted

on all sides and above.

Unit has legs for mounting on level pad. See Fig. 2

and

Table

1

for

weight

distribution

based

on

recommended support points.

NOTE: If vibration isolators are required for a par­

ticular installation, use the data in Table 1 and Fig. 2
to make proper selection.

Step 2 — Rig and Locate the Unit

A

CAUTION

Be sure unit panels are securely in place prior to
rigging.

Be

careful

rigging,

handling

and

installing

unit. Improper unit location can cause system mal­

function and material damage.

RIGGING — Lift units at points 3, 4, 7, 8 (Fig. 2). Use

eyebolts and washers supplied in parts package. Do not
sling unskidded unit. Skidded unit may be slung provided

sling does not contact sides of unit. While unit is on skid,
it can be rolled or dragged.

IMPORTANT: SPREADER BARS MUST BE USED BETWEEN POINTS

3-4 AND 7-8

2

8

4

6

COIL

SECTION

+

+

COMPR

SECTION

TOP VIEW

Bo

LEG LOCATIONS

-H LIFTING POINTS

Fig. 2 — Weight Distribution

PLACING UNIT — Place unit so that airflow is un­
restricted

above.

Provide

clearance

around

the

unit

as

shown in Fig. 1. Remove 6 hold-down bolts, releasing
skid. The legs are attached to base skid.

Block up or suspend unit. With bolts supplied, secure

legs (see Fig. 5) to unit (1, 2, 3, 4, 5 and 6 in Fig. 2 and

Table 1).

Table 1 — Weights

UNIT

38AQ

TOTAL

WEIGHT (lb)

Leg Location

1

2

3

4

5

6

024

2040

204

204

670

670

146

146

028

2160

203

203

592

642

235

285

034

2500

286

286

834

834

130

130

The unit may be mounted on a full pad or on raised

supports at each leg. Weight distribution shown in Fig. 2
will determine type of support required. Bolt unit securely
to pad or supports when positioned and leveled.

Step 3 — Mount Compressor

COMPRESSOR

MOUNTING

As

shipped,

the

com­

pressor

is held

down by special self-locking

bolts and

lockwashers.

After

unit

is

installed,

remove

self-locking

bolts one at a time and reassemble with flanged washers
and neoprene snubbers as shown in Fig. 4. The flanged
washers and neoprene snubbers are shipped in a cloth
bag tied to one of the compressor feet. Tighten all 4
bolts, then loosen each until the flanged washer can be
moved sideways with finger pressure.

Step 4 — Complete
Connections

Refrigerant Piping

SIZE

REFRIGERANT

LINES

Consider

length

of

piping

required

between

outdoor

and

indoor

units,

amount of liquid lift and compressor oil return. Refer to

Part 3 of Carrier System Design Manual for line sizing

information.

Refer

to

indoor

unit

installation

instruc­

tions for additional information.

Maximum

liquid

line

length

is

100

feet.

Carefully

determine the minimum expected unit capacity and size
interconnecting

lines

accordingly.

For

low

load

condi­

tions, determine if there is a need for double suction
risers per Carrier System Design Manual. Consider vapor
line as hot gas line. Consider line sizes for heating as well
as cooling capacities.

A CAUTION

Piping must be properly sized and installed for the
system to operate efficiently.

FILTER

DRIERS

38AQ

units

have

factory-installed

filter driers. It is not necessary to add filter drier and check
valve arrangements in interconnecting piping. It is recom­
mended that a field-supplied liquid moisture indicator be

installed in liquid line. Indoor units provide filter driers
with

heat

pump

piping

packages,

for

field

installation.

Refer to indoor unit installation instructions for details.

Complete refrigerant piping from indoor coil to out­

door coil before opening liquid and suction lines at the
heat pump unit. See Table 3 for proper refrigerant charge

and piping selection data.

PROVIDE

SAFETY

RELIEF

A

fusible

plug

is

located on the liquid line before the liquid valve and on
top of the accumulator (Fig. 3). DO NOT CAP THIS
PLUG.

If

local

code

requires

additional

safety

devices,

install as directed.

HEAD PRESSURE CONTROL — Fan cycling for head

pressure control is a standard offering but functions in
cooling mode only. The no. 2 fan cycles as a function of
liquid

pressure

sensed

by

fan

cycling

pressure

switch

(FCPS). Fan no. 3 cycles as a function of outdoor air

temperature

through

the

action

of

the

air

temperature

switch (ATS). See Table 2 for settings. These switches are

automatically bypassed in heating mode. Table 4 shows

minimum

outdoor

ambient

temperatures

at

which

units

will operate and provide full cooling capacity.

RECEIVER — No receiver is provided with the unit; it
is recommended that one not be used.

PIPING

PROCEDURE

Do

not

remove

caps

from

vapor and liquid line stubs in compressor compartment
until piping connections are ready to be made. Pass nitro­
gen or other inert gas through piping while brazing, to

prevent formation of copper oxide.

Install

thermostatic

expansion

valves

in

liquid

line

ahead of each indoor coil section.

Advertising
This manual is related to the following products: