Fig. 3 — component locations, Table 2 — physical data – Carrier 38AQ034 User Manual
Page 3
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

SUCTION
PIPING
AT
INDOOR
COIL
AND
TXV
BULB
LOCATION
—
The
purpose
of
these
recom
mendations
is
to
achieve
good
mixing
of
refrigerant
leaving indoor coil suction header for proper sensing by
the TXV bulb.
1.
A minimum of two 90° elbows must be installed
upstream of the expansion valve bulb location.
2.
The TXV sensing bulb should be located on a vertical
riser where possible. If a horizontal location is neces
sary, secure the bulb at approximately the 4 o’clock
position.
3.
Size suction line from indoor coil through the riser
for high velocity. Enter suction pipe sizing charts in
the
Carrier
System
Design
Manual
at
design
tons
and equivalent length (for 2 F loss). If reading falls
between 2 sizes on chart, choose the smaller pipe size.
Suction piping for the high velocity section should be
selected for about 0.5 F friction loss. If a 2 F loss is
allowed for the entire suction line, 1.5 F is left for the
balance of the suction line and it should be sized on
that basis. Check that high-velocity sizing is adequate
for oil return up the riser.
When the compressor is below indoor coil, the riser
at indoor coil does not have to extend as high as the
top level. After a 15 diameter riser has been provided,
suction line may elbow down immediately.
Table 2 — Physical Data
UNIT 38AQ
024
028
034
OPERATING W EIGHT (lb)
2040
2160
2500
REFRIGERANT
R-22
Operating Charge (ib)*
55
61
71
COMPRESSOR
Model No
06E2250
06E6265
06E2275
Cylinders
4
6
6
Oil (pts)
14
19
19
Crankcase Heater (watts)
180
OUTDOOR AIR FANS
Number
3
Rpm; 60-Hertz
1140 (3-Ph); 1075 (Single-Phase)
Diameter (in )
26
30
30
Motor Hp
3/4
1
1
Cfm
15 000
24 000
24 000
Kilowatts
3 4
3 4
3 6
OUTDOOR COIL
Rows Deep . Fins/Inch
3 15
Face Area (sq ft)
35 4
39 0
49 6
Storage Capacity (lb|t
70
1
99
CONTROLS
High Press Switch (HPS)
Cutout (psig)
426 ± 7
Cut-in (psig)
320 ±20
Loss-of-Charge Switch (LCS) —
Liquid Line
Cutout (psig)
5 ±3
Cut-in (psig)
20 ±5
UNIT38AQ
024 1 028
034
CONTROLS (cont)
Fan Cycling Press Switch (FCPS)—
No 2 Fan Cycling
Opens (psig)
126 ±4
Closes (psig)
257 '¿S
THERMOSTAT
Defrost Thermostat (DFT)
Opens (F)
Closes (F)
65 ±5
28 ±3
Fan Cycling Thermostat (ATS) —
No 3 Fan Cycling
Opens (F)
Closes(F)
70 ±3
83 max
FUSIBLE PLUG SETTING
Liquid Line (F)
Accumulator (F)
210 ±10
170 ±10
OIL PRESS SAFETY SW ITCH (OPS)
Set Point (psig)
Differential (psig)
9
28
'Approximate charge with 25 ft of interconnecting piping Use appropriate
charging charts for actuai charging of unit
fRefrigerant storage capacity at 120 F condensing temperature with con
denser 80% fuli of iiquid
FUSIBLE PLUG
FUSiBLE PLUG
ACCUMULATOR
LOSS-OF-CHARGE SW ITCH
FAN CYCLING PRESSURE
SW ITCH
DEFROST THERMOSTAT
AIR TEMPERATURE
SW ITCH
COMPRESSOR
UNLOADER
SOLENOID
MUFFLER COMPRESSOR
SERVICE
VALVE
Fig. 3 — Component Locations