A caution – Carrier 38AQ034 User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

To Charge System

— Refer to Carrier Standard

Serviee

Teehniques

Manual,

Chapter

1

and

the

pro-

eedures

described

below.

Use

Fig.

8

for

charging

any

40RR/38AQ024

combination;

Fig.

9

for

charging

any

40RR/38AQ028

combination;

and

Fig.

10

for

charging

any 40RR/38AQ034 combination.

A CAUTION

Charge unit in cooling mode only.

Charging unit

in heating mode could result in overcharging.

1. Use Refrigerant R-22 only.

2.

Regulate refrigerant drum valve to maintain suction

pressure at 80 psig while charging. Charge with vapor
only at suction side of unit.

NOTE: Do not depend on sight glass when charg­
ing unit. Use charging chart.

3.

Allow system to operate for 20 minutes.Take tem­

perature and pressure readings at liquid service valve
and check values with the charging chart.

4.

Measure liquid line temperature close to the liquid

service valve, and the pressure at the Schrader port on
the liquid line service valve. Plot point on the charging
chart. If point is above the line, add charge. If point
is below the line, remove charge until operating point

falls on the line.

5. Record final refrigerant charge on unit nameplate.

To Start Unit — After compressor crankcase
heater has been on for at least 24 hours,

set room

thermostat so unit will start on desired mode.

HEATING

Place

thermostat

selector

at

HEAT

and

set temperature selector above room ambient.

COOLING

Place

thermostat

selector

at

COOL

and

set temperature selector below room ambient.

NOTES:
1. All 3 outdoor fans must be operating

2 To be used with approved 40RR combinations only.

3. Applies to all approved combinations

Fig. 9 — Cooling Cycle Charging Chart, 40RR/38AQ028

7

Advertising