Service, Compressor motor protection, Lubrication – Carrier 38AQ034 User Manual
Page 9: Fig. 11 — fan adjustment
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
SERVICE
Capacity Control
is
by
one
electrically
actuated
unloader which controls 2 cylinders. Unloader does not
require field adjustment.
Compressor Motor Protection
CIRCUIT
BREAKER
—
A
manual
reset
calibrated-trip
magnetic circuit breaker protects the compressor against
overcurrent. Do not bypass connections to increase size
of breaker for any reason If trouble occurs, determine
cause
and
correct
before
resetting
the
breaker.
Circuit
breaker Must Trip Amps (MTA) are listed in Tableó,
Electrical Data.
DISCHARGE GAS THERMOSTAT — A sensor in the
discharge gas of the compressor reacts to excessively high
discharge
gas
temperature
and
shuts
off
compressor.The
high temperature of discharge gas is a direct indication
of an overtemperature condition in compressor motor.
CRANKCASE
HEATER
—
The
compressor
has
an
electric heater located in the bottom cover, held in place
by a clip. Heater musi be tight to prevent backing out
(heater will burn out if exposed to air). The heater is
wired into compressor control circuit through a relay to
energize only when compressor shuts off. This keeps the
oil at a temperature that will prevent excessive absorption
of refrigerant during shutdown periods. Crankcase heater
is located in a lockout circuit. If crankcase heater is defec
tive,
the
compressor
locks
off
Heat
pump
remains
off
until
corrective
action
is
taken.
This
lockout
circuit
cannot be reset by adjusting the thermostat.
Crankcase heater should be energized at all times when
unit
is
not
running
except
during
prolonged
shutdown
or
during
servicing.
In
these
cases,
heater
should
be
energized for 24 hours before unit is restarted.
Fan Motor Protection
— Fan motors are inherently
protected, grouped on a single circuit breaker.
Fan Adjustment
— When replacing a fan, adjust fan
until top surface of hub plate is below top of orifice ring
as
indicated
in
Fig
11.
Then,
tighten
both
setscrews,
located over the keyway of fan hub of motor shaft. Seal
recessed area of fan hub bore with Permagum to prevent
rusting.
Head Pressure Control
reduces condensing capacity
under
low-ambient
conditions.
For
intermediate
season
operation, fan cycling is employed. Fan no. 2 is cycled by
pressure control, with the pressure sensor located in the
liquid line. Fan no. 3 is cycled by an air temperature
thermostat (see Table 2).
Liquid Line Solenoid Valve
closes when compressor
is off, and opens when compressor is on. The valve mini
mizes refrigerant migration during heat pump OFF cycle,
protecting against flooded starts.
Accumulator Oil Return
is
external.
The
accu
mulator
drains
through
an
extenal
port
at
bottom
of
accumulator. The port feeds an orifice which regulates the
rate of oil and refrigerant returned to the compressor. The
orifice is removable and cleanable when the system does
not
contain
refrigerant.
The
oil
return
mechanism
also
contains a solenoid valve that opens when compressor is
ON, and closes when compressor is OFF. The oil return
solenoid does not allow liquid refrigerant to drain from
the accumulator during the heat pump OFF cycle, pro
tecting the compressor against flooded starts.
Lubrication
FAN MOTORS — Fan motors have permanently lubri
cated bearings. No provisions for lubrication are made.
COMPRESSOR
—
The
compressor
has
its
own
oil
supply. Loss of oil due to a leak in the system should be
the only reason for adding oil after system has been in
operation.
Coil Cleaning
— Clean coils with a vacuum cleaner,
fresh water, compressed air or a bristle brush (not wire).
Set up coil cleaning as part of a planned maintenance
schedule
when units
are
installed
in
corrosive environ
ments. Wash all accumulations of dirt from coil in these
applications. Keep condenser coil drain holes free of dirt
and debris to ensure adequate coil drainage.
UNIT
DIMENSION A (in.)
38AO
Center Fan
End Fan
024
%
%
028
034
1%
2%
Fig. 11 — Fan Adjustment