Service, Compressor motor protection, Lubrication – Carrier 38AQ034 User Manual

Page 9: Fig. 11 — fan adjustment

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

SERVICE

Capacity Control

is

by

one

electrically

actuated

unloader which controls 2 cylinders. Unloader does not
require field adjustment.

Compressor Motor Protection

CIRCUIT

BREAKER

A

manual

reset

calibrated-trip

magnetic circuit breaker protects the compressor against
overcurrent. Do not bypass connections to increase size
of breaker for any reason If trouble occurs, determine

cause

and

correct

before

resetting

the

breaker.

Circuit

breaker Must Trip Amps (MTA) are listed in Tableó,

Electrical Data.

DISCHARGE GAS THERMOSTAT — A sensor in the

discharge gas of the compressor reacts to excessively high
discharge

gas

temperature

and

shuts

off

compressor.The

high temperature of discharge gas is a direct indication
of an overtemperature condition in compressor motor.

CRANKCASE

HEATER

The

compressor

has

an

electric heater located in the bottom cover, held in place

by a clip. Heater musi be tight to prevent backing out

(heater will burn out if exposed to air). The heater is
wired into compressor control circuit through a relay to
energize only when compressor shuts off. This keeps the

oil at a temperature that will prevent excessive absorption
of refrigerant during shutdown periods. Crankcase heater
is located in a lockout circuit. If crankcase heater is defec­
tive,

the

compressor

locks

off

Heat

pump

remains

off

until

corrective

action

is

taken.

This

lockout

circuit

cannot be reset by adjusting the thermostat.

Crankcase heater should be energized at all times when

unit

is

not

running

except

during

prolonged

shutdown

or

during

servicing.

In

these

cases,

heater

should

be

energized for 24 hours before unit is restarted.

Fan Motor Protection

— Fan motors are inherently

protected, grouped on a single circuit breaker.

Fan Adjustment

— When replacing a fan, adjust fan

until top surface of hub plate is below top of orifice ring

as

indicated

in

Fig

11.

Then,

tighten

both

setscrews,

located over the keyway of fan hub of motor shaft. Seal
recessed area of fan hub bore with Permagum to prevent
rusting.

Head Pressure Control

reduces condensing capacity

under

low-ambient

conditions.

For

intermediate

season

operation, fan cycling is employed. Fan no. 2 is cycled by
pressure control, with the pressure sensor located in the
liquid line. Fan no. 3 is cycled by an air temperature
thermostat (see Table 2).

Liquid Line Solenoid Valve

closes when compressor

is off, and opens when compressor is on. The valve mini­
mizes refrigerant migration during heat pump OFF cycle,

protecting against flooded starts.

Accumulator Oil Return

is

external.

The

accu­

mulator

drains

through

an

extenal

port

at

bottom

of

accumulator. The port feeds an orifice which regulates the
rate of oil and refrigerant returned to the compressor. The
orifice is removable and cleanable when the system does
not

contain

refrigerant.

The

oil

return

mechanism

also

contains a solenoid valve that opens when compressor is
ON, and closes when compressor is OFF. The oil return
solenoid does not allow liquid refrigerant to drain from
the accumulator during the heat pump OFF cycle, pro­
tecting the compressor against flooded starts.

Lubrication

FAN MOTORS — Fan motors have permanently lubri­

cated bearings. No provisions for lubrication are made.

COMPRESSOR

The

compressor

has

its

own

oil

supply. Loss of oil due to a leak in the system should be
the only reason for adding oil after system has been in
operation.

Coil Cleaning

— Clean coils with a vacuum cleaner,

fresh water, compressed air or a bristle brush (not wire).
Set up coil cleaning as part of a planned maintenance
schedule

when units

are

installed

in

corrosive environ­

ments. Wash all accumulations of dirt from coil in these

applications. Keep condenser coil drain holes free of dirt
and debris to ensure adequate coil drainage.

UNIT

DIMENSION A (in.)

38AO

Center Fan

End Fan

024

%

%

028
034

1%

2%

Fig. 11 — Fan Adjustment

Advertising
This manual is related to the following products: