542E REQUIRED CLEARANCE (Inches)

Top of unit.................................. 48 Blower access door end______ 30

Duct side of unit......................... 12 End opposite blower
Compressor access door

access end...........................12

side......................................... 30 Bottom of unit above

anticipated snow level.... 6

OUTDOOR FAN

CONTROL ACCESS DOOR

COMPRESSOR
ACCESS DOOR

ELECTRIC HEAT

HIGH-VOLTAGE INLET WITH
MULTIPLE KNOCKOUTS

A79071

542E DIMENSIONS (Inches)

Size

A

B

c

D

E

F

G

H

J

024 & 030

60-3/16

32-3/16

24-13/16

21

11-1/2

13-5/16

57

6-7/8

6-15/16

036

60-3/16

32-3/16

24-13/16

21

13-3/4

13-5/16

57

4-5/8

6-15/16

042, 048, & 060

68-3/16

40-3/16

30-13/16

21

16-3/8

17-5/16

65

5-1/8

7-1/2

Sizes

K

L

M

N

P

R

S

T

TJ

V

024 & 030

18-1/8

1-1/2

15-3/32

12-9/16

14-1/2

28-9/16

37-1/8

2

7/8

27-7/8

036

18-1/8

1-1/2

15-3/32

12-9/16

14-1/2

28-9/16

37-1/8

2

7/8

27-7/8

042, 048, & 060

25

1-1/2

20-3/32

15-1/8

18-1/2

34-9/16

44-1/4

2

7/8

35-3/16

Figure 3—542E Dimensional Drawing

TABLE l-RATiNGS, PERFORMANCE, & RECOMMENDED FILTER SIZES

MODEL

542E

5420

SIZE

024

030

036

042

048

060

060

SERIES

A

A

A

A

A

A

A

Rated Heating Capacity @ 47°F (Btuh)*

**

26,000

30,000

35,000

42,000

48,000

58,000

58,00011

Total Power Consumption (Watts)*

2850

3450

3850

4600

5100

6300

6300tt

COP*

2.7

2.5

2.7

2.7

2.8

2.7

2.7t-

Rated Heating Capacity® 17°F (Btuh)*

13,500

16,000

18,000

21,000

25,000

31,000

31,00011

Total Power Consumption (Watts)*

2350

2900

3000

3700

4150

5300

530011

COP*

1.7

1.6

1.8

1.7

1.8

1.7

1.711

Rated Cooling Capacity @ 95°F (Btuh)*

25,500

30,000

35,000

41,000

47,000

57,000

57,00011

Total Power Consumption (Watts)*

3350

3900

4650

5150

6100

7600

7600-t

EER

7.6

7.7

7.5

8.0

7.7

7.5

7.511

Rated Indoor Airflow (Ft^/Min)*

850

1050

1300

1535

1700

2000

200011

Rated External Statio Pressure (In. wc)*

0.10

0.15

0.15

0.15

0.20

0.20

0.2011

ARI Sound Rating Humbert

19

19

19

18

18

20

20

Recommended Minimum Filter Size (Sq ln.)t

Standard-Type

408

504

624

737

816

960

**

Cleanable-or High-Capacity-Type

265

328

406

479

530

624

**

* Rated in accordance with ARI Standard 240-77.
t Rated in accordance with ARI Standard 270-75.
f Recommended field-supplied filter sizes shown are based on a velocity of 300 ft/min at the rated indoor airflow.

**Two 20

X

20

X

1 air filters are furnished with Model 542D060.

ttTo achieve the performance ratings indicated, the fresh-air and exhaust openings of the plenum section must be sealed airtight, the

fresh-air damper must be insulated, and the plenum section must be supported by a curb around an opening to the indoor airspace.

-

2

-