Carrier 542E User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

NOTE: Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper charge.

An operating pressure/temperature tag is fastened inside
the compressor compartment. (Also see Tables IV and V.)
Use this tag to approximate the charge if ARI rating condi­
tions can not be obtained, when evaluating the refrigerant

charge by checking operating pressures and temperatures.
This method of evaluating ensures that an optimum
refrigerant charge is in the system when the system condi­
tions and components are normal; however, adjusting the

refrigerant charge does not solve or fix system abnor­
malities.

The amount of refrigerant charge affects how efficiently and
economically the unit operates. An overcharged or under­
charged unit leads to diminished efficiency, high operating

costs, and the possibility of premature compressor failure.

CÀUTION; When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must
always be very minimal. If a substantial adjustment is indi­
cated, an abnormal condition exists somewhere in the

system; such as insufficient airflow across either coil or both
coils.

When checking the refrigerant using the temperature/pres-
sure evaluation method, adhere to the following criteria:

1. Check refrigerant charge in cooling mode when outdoor

temperature is above 65°F.

2. Check refrigerant charge in heating mode when outdoor

temperature is below 65°F.

3. For best results, do not operate unit continuously for

more than 10 minutes if for any reason charge must be
checked in opposite mode above or below 65°F.

Proceed as follows to evaluate the system performance and
refrigerant charge:

1. Remove caps from low- and high-pressure service fit­

tings. See Figure 8.

2. Attach low- and high-side pressure gauge hoses to low-

and high-pressure service fittings, respectively. Hoses

must have valve core depressors. Gauges must be cali­
brated for accuracy.

3. Set room thermostat below room temperature to start

cooling operation or above room temperature to start
heating operation, depending on outdoor temperature.
Allow unit to operate until conditions stabilize and
pressures level out.

4. Determine and record these conditions:

a. Low- and high-side pressures.
b. Dry-bulb
temperature of inlet air at outdoor coil.

c. Temperature of inlet air at return-air grille—creí

bulb if operating in cooling mode or dry bulb if operat­
ing in heating mode.

5. Evaluate system performance and refrigerant charge by

comparing recorded reading with operating pres­
sure/temperature tag.

6. Make slight adjustment to refrigerate charge when

necessary.

NOTE: If the problem causing the inaccurate readings is a

refrigerant leak, see Section V, part B, of these instructions.

C. Indoor Airflow & Airflow Adjustments
CAUTION; The recommended indoor airflow is 350 to 450

ft®/min per each 12,000 Btuh of rated unit capacity. Inade­
quate airflow can cause unsatisfactory operation and per­
formance.

Model 542E, sizes 024 thru 048, and single-phase 060-size
units have direct-drive blower motors. All motors have a

high- and low-speed connection (except for 460-V motors
which have only a high-speed connection).

The system airflow for all direct-drive units (except 460-V)
can be changed, when necessary, by changing the blower
motor speed connection from the factory setting to the
unused speed connection. The factory setting is indicated on
the unit wiring label. For operation of units designed for
208-V and 230-V operation, a blower motor speed connection
may need to be changed. See unit wiring label. See Section
IV, part B, for the procedure.

Model 542D060 and 542E060 3-phase units have belt-drive
blower motors. The system airflow for these units can be
changed, when necessary, by adjusting the blower-motor
pulley as follows:

CAUTION: Increasing the hlower speed places a heavier

load on the motor and increases the current. Do not exceed
the rated full load amperage indicated on the rating plate of
the blower motor.

1. Turn off power at disconnect switch.

2. Relieve belt tension, then remove drive belt from motor

pulley.

3. Loosen setscrew in movable flange on motor pulley and

turn flange either in to increase airflow or out to decrease

airflow.

4. Make sure that setscrew is over flat surface on pulley

hub and tighten setscrew.

5. Replace belt and adjust belt tension for approximately

one inch of sag under normal finger pressure midway
between pulleys.

Tables VI and VII show the air delivery performance at
various external static pressues. Determine the airflow for
the system being installed as follows;

1. Start the unit and measure static pressure in duct

system at unit.

2. Refer to Table VI or VII and determine airflow at static

pressure measured.

NOTE: Be sure that all supply- and return-air grilles are

open, free from obstructions, and adjusted properly.

When using an accessory electric heater, the system airflow
can also be determined by measuring the temperature rise
through the unit, then using the following formula:

AIRFLOW (ftVmin) =

KW

TR

xY

where,
KW = Heater nominal KW at 240 or 480V

TR = Measured temperature rise
Y =

200V

208V

220V

230V

240V

440V

460V

480V

2195

2374

2655

2902

3160

NOTE: Value Y varies with the operating voltage at the heater.

Interpolate to determine the value of Y for voltages not

shown.

CAUTION: When using an accessory electric heater, the

system airflow must be sufficient to prevent the heater limit
switches from tripping off. W'hen using the 20-KW single­
phase heater, the system airflow must be at least 1000

ft^/min.

-

1 0

-

Advertising
This manual is related to the following products: