Isalsa, Troubleshooting chart-heating cycle – Carrier 50QQ User Manual

Page 16

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

TROUBLESHOOTING CHART-HEATING CYCLE

POWEfI CinCU

SUPPLEMENTAL HEAT
RELAY ENERGIZED
OR WIRED WRONG

COMPRESSOR
POWER SUPPn
OPEN

FAULTY START CAP
OR RELAY ISINGLE
PHASEl OR PTC

INDOOR FANS
CYCLING ON
OVERLOAD

OVERCHARGE OR
NONCONDENSABLES
IN SYSTEM

RESTRICTED OR
STUCK
METERING DEVICE

LOW LINE VOLTAGE
OH UNBALANCED
1 PHASF LINE

DEFFI IIVF HUN
(,APA

î

:HOH

iSINLiie PHASF I

REVERSING VALVE
JAMMED IN MID
POSITION

LOOSE LEADS A
OUTDOOR FAN
MOTOR

DEFROST BOARO
NC CONTACTS
OPEN

METERING DEVICE
RESTRICTED OR
ICE CLOGGED

UNDERCHARGED

DEFROST T STAT
IN POOR PHYSICAL
CONTACT WITH LINE

DEFECTIVE DEFROST
RELAY OR DEFROST
TIMER

BAD ELECTRICAL CON
NECTION ANYWHERE
IN DEFROST CIRCUIT

OUTDOOR
THERMOSTAT
DEFECTIVE

CAP TUBE PINCHED
OR BULB NOT
SENSING TRUE OOT

STRIP HEATER RELAY
OR CONTACTOR
DEFECTIVE

OPENING IN POWER
CIRCUIT TO HEATER
ELEMENTS

OPEN (KLIXONI
OVERTEMPERATURE
THERMOSTAT

DEFECTIVE ROOM
THERMOSTAT
I2ND STAGE)

TROUBLESHOOTING CHART—COOLING CYCLE

NO COOLING OR
INSUFFICIENT COOLING

COMPRESSOR
WILL NOT RUN

CONTACTOR OPEN

OPENING IN
POWER CIRCUIT

DEFECTIVE LOW
VOLTAGE
TRANSFORMER

CONTACTOR OR
COIL DEFECTIVE

INTERNAL OVERLOAD
OPEN

CONTACTOR CLOSED

FAULTY START CAP
OR RELAY (SINGLE
PHASE) OR PTC

COMPRESSOR STUCK

COMPRESSOR RUNS
BUT CYCLES ON 8i OFF

INTERNAL OVERLOAD

OUTDOOR FAN STOPPED
OR CYCLING ON
OVERLOAD

LOOSE LEAD AT
FAN MOTOR

DEFROST BOARD
N C CONTACTS

MOTOR DEFECTIVE

OUTDOOR AIR
RESTRICTED OR
RECIRCULATING

COMPRESSOR HOT

REVERSING VALVE
IN MID POSITION

LINE VOLTAGE

LOW LINE VOLTAGE
OR UNBALANCED
3 PHASE

DAMAGED
REVERSING
VALVE

RESTRICTED
DISCHARGE
LINE

OVERCHARGE OR
NONCONDENSABLES
IN SYSTEM

LOW
REFRIGERANT
CHARGE

DIRTY AIR FILTERS

DUCT RESTRICTED

COIL FROSTED

LIOUID LINE
SLIGHTLY
RESTRICTED

METERING DEVICE
RESTRICTED

COMPRESSOR RUNS
INSUFFICIENT COOLING

HIGH SUCTION
LOW HEAD
PRESSURE

REVERSING VALVE
HUNG UP OR
INTERNAL LEAK

DEFECTIVE
COMPRESSOR
VALVES

COMPRESSOR
FLOODING

UNIT
OVERCHARGED

INTERNAL
PRESSURE
RELIEF OPEN

RESTRICTED
OR STUCK
METERING DEVICE

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

BookI 1 I 4

PC 101 Catalog No. 565-097

Printed in USA

Form 50QQ-8SI Pg 16

11-87

Replaces: 50QQ-7SI