Carrier 39B User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Fig. 7 — Assembly of Accessory Bypass Duct — (Arrangement A Only)

d.

Fasten flange 2 to matching surface of

cooling

coil

section

with

seven

1/4-20 X 1/2-in. self-tapping screws and

matching surface engagement holes.

e. Fasten top panel to each flange 3 and 4 with

two and three 1/4-20 x 1/2-in. self-tapping
screws respectively per end and each
flange 3 and 4 engagement holes.

f.

Fasten one angle 5 to each flange 6 with

three 1/4-20 X 1/2-in. self-tapping screws
and flange 6 engagement holes.

g. Tighten all screws securely.

2. Sizes 135 and 140—

a.

Place one endpiece on one flange 8 of

cooling coil section with fiber glass insulated

side facing second flange 8.

b. Fasten flange 10 to 8 as follows;

(1) Line up flange 10 and 8. Ensure air in­

take side of bypass duct is flush with
edge of flange 9

(2) Drill six engagement holes in flange 8

with a no. 3 drill.

(3) Fasten flange 10 to 8 with six

1/4-20 X 1/2-in. self-tapping screws.

c. Loosely fasten one end of top panel to flange

12 with nine 1/4-20

X

1/2-in. self-tapping

screws and flange 12 engagement holes.

d. Place second endpiece on second flange 8 of

cooling coil section with fiber glass insulated

side facing first endpiece.

e. Loosely fasten remaining end of top panel

with nine 1/4-20 X 1/2-in. self-tapping

screws and flange 12 engagement holes.

f.

Loosely fasten front panel to flanges 13

with five 1 /4-20 x 1 /2-in. self-tapping screws

per end and flange 13 engagement holes.

g. Loosely fasten flange 14 to matching edge

of top panel with seven 1/4-20 x 1/2-in.
self-tapping screws and engagement holes
along top panel edge.

h.

Fasten flange 10 of second endpiece as

follows:

(1) Line up flange 10 and 8. Ensure air

intake side of bypass duct is flush with

edge of flange 9.

(2) Drill six engagement holes in flange 8

with a no. 3 drill.

(3) Fasten flange 10 to 8 with six

1/4-20 X 1/2-in. self-tapping screws.

i.

Fasten flange 11 to matching surface of

cooling coil section as follows:

(1) Line up flange 11 and matching surface.

(2) Drill ten engagement holes in matching

surface with a no. 2 drill.

(3) Fasten flange 11 to matching surface

with ten 1/4-20

X

1/2-in. self-tapping

screws.

j. Tighten aU screws securely.

FACE AND BYPASS DAMPER SECTION; PRE­
HEAT

COIL

SECTION

AND/OR

SPRAY

HUMIDIFIER SECTION WITH AND WITHOUT
BYPASS (Sizes 070 thru 120) - Refer to Fig. 8.

1. Remove shipping crate(s) and apply sealing tape

to flanges on air discharge side of spray
humidifier section only.

2. Face air discharge side of accessory(ies) toward

air intake side of cooling coil section.

NOTE; Spray humidifier section must be
adjacent to cooling coil section so excess
water can be collected in condensate pan.
Remove factory-installed accessories to do
this and replace same.

10