Fig. 8 — Assembly of Accessory Face and Bypass Damper Section; Preheat Coil Section

and/or Spray Humidifier Section with and without Bypass — (Sizes 070-120)

3. Fasten flanges 2 thru 5 of preheat coil or spray

humidifier section without bypass to matching
flanges of cooling coil section with the following:

a.

Fasten flanges 2 and 3 with three

3/8-16

X

3/4-in. hex head cap screws per

two flanges and matching flange weld nuts.

b. Fasten flanges 4 and 5 with three 3/8-16 x

3/4-in. hex head cap screws and hex nuts per
two flanges.

4. Duct extension (for accessories with bypass) —

a.

Preheat coil section only - Remove two

(size 070) or three (sizes 080 thru 120)

1/4-20x1-in. hex head cap screws, plain

washers, and hex nuts from each flange 6
and 7. Save fasteners for following steps b
and c.

b. Place endpiece having largest holes on side

C, on flange 6 of accessory. Face fiber glass
insulated side toward flange 7 of accessory.
Fasten surface A to flange 6 of spray

humidifier section with one 1/4-20 x 1/2-in.
self-tapping screw and flange 6 engagement
hole. For preheat coil section, use two of
each type of fastener saved from preceding
step a.

c.

Place second endpiece on flange 7 of

accessory. Face fiber glass insulated side
toward fiber glass insulated side of first
endpiece. Fasten surface A to flange 7 per
preceding step b.

d. Fasten one angle D to each side E of both

endpieces with two (size 070) or three
(sizes 080 thru 120)

1/4-20 x 1/2-in. self­

tapping screws per angle and side E engage­

ment holes.

e. Fasten top panel to top of each endpiece

with one (spray humidifier section) or two
(preheat coil section) 1/4-20 x 1/2-in. self­
tapping screw(s) per end and engagement
hole(s) in top of each endpiece.