Electric Furnace

Installation Instructions

Non-Ducted Return Air Closet Installation

The cabinet can be installed in a closet with a false bottom to form
a return air plenum, or mounted on an open platform inside the
closet. Platform should be high enough to provide a free (open)
area for adequate return airflow into the bottom of the cabinet.
The open area can be on the front side or a combination of front
and sides, providing there is clearanoe on the sides between oabi-

net and closet. Refer to ACCA Manual D for sizing and free

area recommendations.

NOTE: Local codes may limit application of systems without a

ducted return to single story dwellings.

Horizontal Left and Right Installations

No Coil

If a coil is not being installed, the cabinet can be placed on either

side for horizontal airflow as shipped. Refer to instructions with
electric heat for instructions on horizontal applications.

With Coil

All units must have the horizontal drain pan kit Installed for either

left or right hand applications, For installation of the drain pan, re­

fer to the installation instructions included with the horizontal drain
pan kit, and the following.

CAUTION

A field-fabricated auxiliary drain pan, with a separate
drain is REQUIRED for all installations over a finished

living space or in any area that may be damaged by

overflow from the main drain pan. In some localities,

local codes require an auxiliary drain pan for ANY hori-

zontai instaiiation.

Drain Pan Installation

1.

Position side of coil drain pan into horizontal drain pan

trough on deep end of pan.

2.

Install the coil support bracket on left or right side of the

cabinet.

3.

Install coil drip flanges on the left or right side of the coil,

(same side as horizontal drain pan).

5. Install drain plugs as required in back side of horizontal

drain pan. Install plugs in A coil drains to prevent air leaks,

5.

Slide coil assembly into cabinet being careful not to tear in­
sulation,

NOTE: Be sure A coil pan fits into the support bracket on the back
side of the cabinet and that pan is under the flange of the bracket
on the right side. The brackets fit over the top edge of the A coil
drain pan to hold it when it's put into the horizontal position,

6.

Referto RestrictorOrifice Selection and change restrictor if

necessary, then install coil access panel.

Cabinet can now be placed on it’s side for horizontal airflow.

Suspended Cabinet Installation

1.

If the cabinet cannot be supported on a frame or shelf, it

may be suspended.

2.

Use metal strapping or threaded rod with angle iron sup­

ports under the auxiliary drain pan to suspend cabinet.
These supports MUST run parallel with the length of the
cabinet (Figure 5 ).

3.

Ensure that there is adequate room to remove service and

access panels after installing supporting brackets.

4.

Place Styrofoam blocks in auxiliary drain pan to support

cabinet.

Duct Connections

Supply Duct

Supply duct must be attached to the outside of flange on outlet
end of unit. Flexible connectors may be used if desired. Maintain
clearances from supply duct to combustibles when heaters are
installed. See Figure 1 and unit rating plate.

Return Duct

Return duct should be attached to bottom of unit using sheet met­

al screws or other fasteners.

m

442

01

2204

01