Blower Coils

Installation Instructions

Sequence Of Operation

Mode

Thermostat to Con­

trol Board 24 volt

Control

State

Control Function

Electric H eat Only

Constant Blower
(Fan Switch ON)

G

On

Fan On.

Off

Fan Off.

Thermostat calls for
Heat

G & W1 & W2

On

Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.

Off

2ndthen1st Stage Of Heat Off. 6 sec delay, then Fan Off.

Cooling Only Unit With Electric Heat

Constant Blower
(Fan Switch ON)

G

On

Fan On,

Off

Fan Off.

Cooling Only Unit
(Thermostat calls for
Cooling)

Y&G

On

Compressor On, Fan On.

Off

Compressor Off, 60 Second Delay - Then Fan Off,

Cooling Only Unit
(Thermostat calls for
Heat)

G & W1 & W2

On

Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.

Off

2ndthen1st Stage Of Heat Off. 6 sec delay, then Fan Off.

Heat Pump Wit 1 Electric Heat

Heat Pump
(Thermostat calls for
Cooling)

Y & G & O

O n

Compressor On, Reversing Valve Energized, Fan On.

Off

Compressor Off, 60 Second Delay And Then Fan Off.

Heat Pump
(Thermostat calls for
Heat)

Y&G

On

Compressor On, Fan On

Heat Pump cannot
maintain proper temp.

Y & G & W1 & W2

On

1 sf Stage Of Heat On, then 2nd Stage Of Heat On

Electric Heat Tempera­

ture satifised

Off

2nd then 1 st Stage Of Heat Off

Heat Pump
(Goes into Defrost
Mode)

Y & G & 0 & W 1 & W 2

O n

Reversing valve switches unit to cooling, 1st Stage Of Heat

On, then 2nd Stage Of Heat On

Off

Reversing valve switches back to heating, 2nd then 1st Stage

Of Heat Off

Heat Pump
(Room temp, satifised)

Y&G

Off

Compressor Off, 60 Second Delay And Then Fan Off.

Heat Pump
(Emergency Heat)

G & W1 & W2

On

Fan On, 1st Stage Of Heat On, then 2nd Stage Of Heat On.

Off

2nd then 1 st Stage Of Heat Off. 6 sec delay, then Fan Off.

NOTE: Electric Heat Elements are controlled by relays with a delay sequence from the logic board to provide sequencing between elements.

Limit Operation

The temperature limit responds to over-temperature conditions in the air duct. If the temperature limit trips, the electric heater relays will
be de-energized and the fan relay will be energized. Once the limit resets, the control will resume normal operation. If the limit trips four

times during a single call for heat, the control will go into a 1 hour soft lockout. During the soft lockout, the fan relay will respond to
thermostat inputs but the heater relays are disabled. If the control detects a limit trip during the soft lockout, the control will go into a hard

lockout. Once in a hard lockout, the fan relay is locked on and the heater relays are disabled. Turning the power to the unit off and then on

will clear this state.