Installation Instructions

Electric Furnace

Electrical Wiring

:zznnnm.

Electrical shock hazard.

Turn OFF electric power at fuse box or service

panel before making any electrical connections
and ensure a proper ground connection is made
before connecting line voltage.

Failure to do so can result in property damage,
personal injury and/or death.

All electrical work MUST conform with the requirements of local
codes and ordinances and the National Electrical Code NFPA 70
current edition.

Electrical Heaters & Operating Controls

The low voltage transformer and the fan control are standard on
all models and are prewired at the factory. To operate the blower
coil, a heater accessory or a no-heat kit must be installed, Line
voltage connections are made to the heater accessory or the no­

heat kit.

Low Voltage Control Connections

The 24 volt power supply is provided by an internally wired low
voltage transformer which is standard on all models. If power
supply is 208 volt, the low voltage transformer must be rewired to
the 208 volt tap. See the unit wiring label.

Field supplied low voltage wiring can enter the unit on the top left
hand corner or the left hand side panel. When using the left hand

side panel entrance, the low voltage wiring must be fed through
the entrance hole in the bottom of the control box.

Install the strain relief bushing (supplied with unit) in the selected
hole and a hole plug (supplied with unit) in the unused hole.

Connect the field wiring at the screw terminals of the control
board. Refer to Figure 9.

Keep the low voltage wiring as short as possible inside the control

box.

Complete connections between indoor blower, outdoor section,

indoor thermostat and electronic outdoor thermostat (accessory)

according to instruction provided with the Condenser Installation

Instructions or those provided with the accessory and refer to Fig­

ure 10.

Install No Heat Kit

If electric heat is not used, install accessory No Heat Kit.

1. , Locate adapter and filler plates, with screws inside pack­

age unless they were preinstalled at the factory.

2. , If necessary, attach adapter plate and filler plate to bracket

as required to match cabinet, Refer to Figure 9.

3. , Secure the no heat accessory with four screws.

4. . Connect the plug from No Heat Kit wiring into the recep­

tacle on the control board on the side of the cabinet.

The power supply wiring to the unit MUST be provided with over­
current protection. Governing codes may require this to be fuses
ONLY or circuit breakers.

For blower cabinets without heaters, a 15 amp circuit may be

used.

Line Voltage Connections

Line voltage wiring may be brought into the unit through the top
right-hand corner or the right-hand side panel. The correct hole
size required by the conduit fitting must be punched at the pilot
hole location. Plug the unused pilot hole with a hole plug (supplied

with unit). Refer to Figure 9 for line voltage connections.

Grounding

Use a copper conductor (#14AWG) from the unit to a grounded

connection in the electric service panel or a properly driven and
electrically grounded ground rod.

Line Voltage Connection

1. A disconnect switch MUST be located within sight of the

unit.

2.

Provide line voltage power supply (208V-240V) from a
separate 15 amp circuit.

3.

Connect line voltage LI and L2 to the lugs on the No Heat
Kit, Figure 9.

Overcurrent Protection

No Heat Kit Technical Data

No Heat

Model

Supply Circuit

Supply

Circuit

No.

Maximum

Motor

AMPS.

Tota!

AMPS.

Branch

Circuit

Ampacity

Maximum

Overcurrent

Protective

Device

(AMPS.)

Recommended

Supply W ire

75

^ C. Copper

Ground

W ire

No.

Size

Max.

Length (Ft)

Volts

Phase

Hertz

No.

Size

AMF001NH

240

1

60

Single

6.0

6.0

7.5

15

2

14

104

1

14

208

1

SO

Single

6.0

6.0

7.5

15

2

14

90

1

14

OJ

442

01

2204

01