Installation Instructions

Electric Furnace

Figure 4

Horizontal Drain Pan

Horizontal Drain Pan
(Left Hand Airflow)

Coil Access Panel

Drip Flanges
(Left Hand Airflow)

Drip Flanges
(Right Hand Airflow)

Coll Support Bracket

Coil Support Bracket
(Lett Hand Airflow)

zontal Drain Pan

(Right Hand Airflow)

38-20-06

Filter Installation

Filters must be field supplied. The blower cabinet is set up for an

internal filter or a remote filter grille or other means may be pro­
vided, Refer to ACCA Manual D for remote filter sizing.

To install an internal filter, remove screw securing filter door and
slide filter into unit. Some filters are marked for airflow direction,
make sure arrow points towards blower if marked. Washable fil­
ters are offered as an accessory. Disposable filter sizes are listed
in Filter Static Pressure Drop Table,

Condensate Drain

The unit is provided with 3/4” National Pipe Thread (NPT) con­
densate drains. (Figure 1). Any drain can be used as a primary or
secondary drain. Condensate drain lines should be installed in a

manner that does not obstruct access to the filter.

There is a secondary drain fitting supplied with the unit that will
convert any of the primary condensate drain connections into a
secondary drain connection. This fitting should be installed in any
of the primary drain connections to convert it to a secondary drain.

1. Connect the drain lines to the appropriate drain fittings. 3/4”

PVC or other type of drain line may be used. The drain line
must not be smaller than the drain fitting,

2. Install a trap in the drain line below the bottom of the drain

pan and pitch the drain lines down from the coil at least I/4”
per foot of run. Horizontal runs over 15 feet long must also
have an anti-siphon air vent (stand pipe), installed ahead
of the horizontal run. An extremely long horizontal run may
require an oversized drain line to eliminate air trapping.