Compartment size, Top view of generator, Compartment construction – Generac Power Systems 00802-3 User Manual

Page 20: Sound insulating materials, Metal uning, Insulation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

COMPARTMENT SIZE

Plan the compartment size carefully. Provide a mini­
mum of at least 1 inch (2” recommended) of clearance
between the generator and compartment walls and 1 inch

(2’

recommended) of clearance between the generator

and the ceiling AFTER you have lined the compart­

ment with metal, and AFTER you have installed sound
insulation (Figure 17).

NOTE: Refer to the "Major Features and Dimensions”
drawing in the back of this manual.

Figure 17 — Provide Clearance Around Generator

PLYWOOD

COMPARTMENT

11NCH MINIMUM CLEARANCE

ON ALL SIDES (2" RECOMMENDED)

TOP VIEW OF

GENERATOR

LT

METAL UNING-

1 INCH
MINIMUM

CLEARANCE
ABOVE
GENERATOR

(2" RECOMMEND­
ED)

INSULATION

COMPARTMENT CONSTRUCTION

The generator compartment should be constructed of 1/2
inch thick plywood. Make the compartment floor a double
thickness of 1/2 inch plywood with the grain of the wood at

cross section for added strength (Figure 18).

Figure 18 — Typical Compartment Construction

• Line the entire compartment interior with 26 gauge galva­

nized steel as described above.

• Line the exterior (underside) of the compartment floor with

26 gauge galvanized steel.

• Vapor seal all compartment seams and joints, to prevent

poisonous, flammable or explosive vapors from entering
the vehicle interior. Refer to the sealant information as

noted previously.

NOTE: Silicone rubber base sealant is an acceptable

caulking material. Pressing putty tape onto compart­
ment joints and seams is NOT acceptable.

• After the compartment has been metal lined and vapor

sealed, line the compartment interior walls and ceiling with

an approved, non-flammable sound insulating material.
See “Sound Insulating Materials.”

DANGER: Do not install sound insulation or any
absorbent material on the compartment floor interi­
or. Such materials will become soaked with com-
bustibie or expiosive vapors and liquids and will
become a fire hazard.

• Openings in compartment walls for passage of electrical

conduit, conductors, hoses, cables, etc., must be made

vapor tight with suitable caulking material.

• Flexible conduit must be sealed internally at the end where it

terminates inside a compartment's electrical junction box!

NOTE: The preceding is required because flexible

conduit, due to its unique construction, is not vapor-
tight along its entire length.

DANGER: Do not install any flammable material
directly above or around the compartment. Heat,
transferred through the compartment structure,
may be sufficient to ignite, char or discolor seat
cushions, fiberboard and other flammable materi­
als. You may need to use approved non-flammable
insulating materials in high temperature areas.

SOUND INSULATING MATERIALS

Once installers have determined that compartments
are properly constructed and metal lined, they can add
acoustical

material.

This

may

include

additional

sealant or insulating material, to reflect noise away

■from the vehicle interior.

Sound insulating materials should be of a non-flamma­
ble type. One excellent insulating material is a 1 inch
thick fiberglass having a 2-poundf density. When fiber­
glass is used, its coated side should face toward the
compartment interior.

Using a combination of sound insulating materials can

often reduce noise more effectively than a single mate­
rial. For example, a sheet of lead or visco-elastic mate­

rial, along with a layer of other acoustical material, is
more effective than when a single material is used.

18

Advertising