Voltage regulator adjustment – Generac Power Systems 91355 User Manual

Page 27

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

• While holding the GOVERNOR SHAFT fully clock­

wise and the GOVERNOR LEVER at wide open
throttle, tighten the GOVERNOR CLAMP BOLT to
70 inch-pounds (8N-m).

3. Start engine, let it stabilize and warm up at no-load.

4. Turn the ADJUSTER NUT to obtain a frequency reading

of 62 Hertz.

5. Determine if the GOVERNOR SPRING is properly locat­

ed In the slot of the GOVERNOR LEVER as follows:

If droop is excessive, move the GOVERONOR

SPRING down one slot on LEVER.

• For greater stability, move the GOVERNOR SPRING

up one slot on LEVER.

6. After repositioning the SPRING on a LEVER slot, recheck

frequency reading and, if necessary, readjust ADJUSTER

NUT to obtain 62 Hertz at no-load.

7. When frequency is correct at no-load, check the AC volt­

age reading. If voltage Is incorrect, the voltage regulator
may require adjustment.

VOLTAGE REGULATOR ADJUSTMENT

The voltage regulator is housed iriside the generator

control panel. Remove the cover and front panel as
shown in Figure 32.

Figure 32 — Removing Cover and Panel

VOLTAGE

REGULATOR

With, frequency at 62 Hertz, AC voltage should read

124 volts. If voltage is incorrect, slowly turn the VOLT­

AGE ADJUST POT on voltage regulator (Figure 33)

until AC voltage is correct.

Figure 33 — Voltage Regulator

25