Caution, Initial power--up, Humidifier connection – Carrier Infinity SYSTXCCUID01- B  User Manual

Page 5: Power up sequence, Ccui d 01 -- b

Advertising
background image

5

be used when connecting to furnace (or fan coil). Ensure connector
is inserted properly into circuit board. (See Fig. 14.)

A B C D

A03193

Fig. 14 -- Wire ABCD Connector

ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in equipment damage

or improper operation.
Improper wiring of the ABCD connector will cause the

Infinity System to operate improperly. Check to make sure all

wiring is correct before proceeding with installation or turning

on power.

CAUTION

!

9. Push any excess wire into the wall. Seal hole in wall to pre-

vent any air leaks. Leaks can affect operation.

10. Attach Infinity Control to the mounting plastic by lining up

the plastic guides on the back of the control with the open-
ing on the mounting plastic and push on.

11. Perform installation of all other system equipment (i.e.

dampers, humidifier, ventilator, UV lights, etc.)

12. Turn on power to equipment.

See wiring diagram, Fig. 11, which includes an indoor
communicating furnace or FE fan coil, with a communicating

outdoor unit. No additional OAT (outdoor air temperature) sensor
is required because the Infinity Control will use the temperature

sensor inside the outdoor unit.
See wiring diagram, Fig. 12, for connecting an indoor
communicating furnace or FE fan coil with a 1--stage air

conditioning unit (non--communicating outdoor). An Outdoor Air
Temperature (OAT) sensor may be installed (but is not required) at

the indoor furnace or fan coil OAT terminals. When OAT sensor is

applied, the Infinity System will provide enhanced system features
and benefits.
See wiring diagram, Fig. 13, for connecting an FE fan coil with a
1--stage heat pump (non--communicating outdoor unit). When

OAT is applied, the Infinity System will provide enhanced system

features and benefits.
NOTE: For other applications not listed, refer to the Network
Interface Module (NIM) Installation Instructions.

Humidifier Connection

A 24VAC bypass or fan powered humidifier may be installed.
NOTE: Do Not Use a traditional humidistat to control humidifier
operation. If a humidifier is installed, let the Infinity Control
operate humidifier.
Bypass Humidifiers
A bypass humidifier should be wired directly to the furnace or fan
coil HUM and 24VAC COM terminals. The Infinity Control will

automatically energize the HUM output during a call for

humidification.
Fan Powered Humidifiers
Most fan powered humidifiers produce internal 24VAC in order to

energize upon a switch or contact closure. For this application, a

24VAC N.O. Isolation Relay (DPST) MUST be used to prevent
mixing the internal humidifier power with the indoor equipment

transformer. Applying 24VAC isolation relay coil to furnace or fan
coil HUM and COM terminals will allow the Infinity Control to

automatically energize the HUM output during a call for
humidification. The N.O. relay contacts will be used to energize the

humidifier. See fan powered humidifier installation instructions for
more details.

EQUIPMENT HAZARD
Failure to follow this caution may result in equipment damage.
Do not apply 24VAC fan powered humidifier (with internal

power supply) direct to indoor unit HUM and COM terminals.

CAUTION

!

HOLD

COOL

HEAT

SCHEDULE

VACATION

PROGRAM

SCROLL

BASIC

ADVANCED

SETUPS

Schedule

to program

temperature

schedule

Vacation

to start/end

vacation

Basic

to set time,

humidity

Advanced

for all other

settings

Scroll

up & down

Fan Button

Display Screen

(LCD)

Right-Side

Button

Heat Button

Cool Button

Temperature

(+/-) Button

System

On/Off Button
Basic & Advanced

Setup Buttons

Flip Down

Door

Left-Side

Button

Humidity/OAT

Button

Hold

Button

Time (+/-)

Button

Schedule & Vacation

Program Buttons

Up/Down

Scroll Buttons

A03194

Fig. 15 -- Functional Overview

INITIAL POWER--UP

NOTE: Refer to Functional Overview (see Fig. 15) to become
familiar with key function buttons such as “System On/Off,”
“Fan,” “Left--Side” and “Right--Side” buttons, etc. These function
buttons will be used frequently during setup.

Power Up Sequence

ESTABLISHING

COMMUNICATIONS

WITH EQUIPMENT

PLEASE WAIT

SOFTWARE

VERSION

INDOOR UNIT

SEARCHING FOR

INDOOR EQUIPMENT

WORKING

OUTDOOR UNIT

SEARCHING FOR

OUTDOOR EQUIPMENT

WORKING

A03195

Fig. 16 -- Power Up Sequence

This section addresses initial power up (or commissioning) of a

new Infinity Control. The User Interface will communicate and
identify all Infinity components in the system. The following is a

typical example for a communicating Variable--Speed Furnace /
Fan Coil with a 2--stage Air Conditioner / Heat Pump (including

Hybrid Heat).
The User Interface display will light up and indicate that it is now
“ESTABLISHING COMMUNICATIONS WITH EQUIPMENT

PLEASE WAIT”. The User Interface will automatically continue
by

“SEARCHING

FOR

EQUIPMENT”,

followed

by

“SEARCHING FOR OUTDOOR EQUIPMENT” (see Fig. 16).

Once the indoor and outdoor equipment has been found, the

CCUI

D

01

--

B