Equipment summary menu, Install menu, Setup menu – Carrier Infinity SYSTXCCUID01- B  User Manual

Page 8: Setup -- thermostat

Advertising
background image

8

INSTALL/SERVICE

EQUIPMENT SUMMARY

INSTALL

SETUP

CHECKOUT

SERVICE

SOFTWARE VERSION 1

EXIT SELECT

A03200

Fig. 22 -- Install / Service Menus

NOTE: The INSTALL / SERVICE menu will automatically exit
after 60 minutes of no push button activity.
EQUIPMENT SUMMARY: Shows all equipment recognized by

and attached to the system.
INSTALL: Used when adding, changing out, or un--installing

equipment.
SETUP: Used to view or modify equipment settings.
CHECKOUT: Allows testing of equipment operation
SERVICE: Used to view operation and fault history of equipment
and enter dealer name/phone number for display

EQUIPMENT SUMMARY MENU

This screen shows indoor unit type and model number, outdoor
unit type (and model number if a 2--stage unit), filter type and any

accessories that are installed are recognized. See Fig. 23.

EQUIPMENT SUMMARY

FURNACE

58MVB0100-12

AC

24ANA136A003

FILTER

EAC

HUMIDIFIER

YES

UV LIGHTS

YES

NO YES

A07025

Fig. 23 -- Equipment Summary

INSTALL MENU

This menu item will perform start--up process in order to learn all

equipment in system. Press right side button to initiate the process.
See Fig. 24.

INSTALL

TO ADD, UNINSTALL OR

RE-INSTALL EQUIPMENT,

PRESS RIGHT SIDE

BUTTON

BACK INSTALL

A03202

Fig. 24 -- Install Menu

SETUP MENU

This menu has several layers, allowing modification of equipment
settings. No settings will need to be made at equipment (i.e. DIP

switches on a furnace). All configuration settings made effective
from this menu will override equipment configuration made by dip

switches. Fig. 25 shows all the information that can be found in the

SETUP menu.

SETUP

THERMOSTAT

FURNACE

HEAT PUMP

ACCESSORIES

SYSTEM MAINTENANCE

BACK SELECT

A03203

Fig. 25 -- Setup Menu

Setup -- Thermostat

Auto Mode Setup:

S

Enable/Disable Auto Changeover mode (default=Enable).

S

Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).

When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until the current cycle is

satisfied and an opposite mode demand has existed for 30 minutes.

If the setpoint is changed, the 30 minute timer is deleted.
Heat/Cool Deadband:

S

0 to 6_F / 0 to 3_C, (default = 2_F)

The minimum difference enforced between heating and cooling
desired temperatures. This can allow one setting to “push” the

other to maintain this difference.
Offsets:
This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the

actual temperature/humidity values (defaults=0).

S

Temperature Offset: --5_F to +5_F (--3_C to +3_C)

S

Outside Temp Offset: --5_F to +5_F (--3_C to +3_C)

S

Humidity Offset: --10 to +10%

Cycles Per Hour:

S

Maximum cycles per hour = 4 (default) or 6.

S

Anticipator = 1 to 9 (default=3). This adjusts sensitivity to
temperature changes. 1 = most sensitive, 9 = least sensitive.

S

If space is over--conditioning, increase the anticipator setting.

S

If space is under--conditioning, decrease the anticipator setting.

Programming:

S

ON (default)-- allows program schedule to be set by user.

S

OFF -- system becomes non--programmable

S

Periods Per Day = 2 or 4 (default=4)

S

Programmable Fan On/Off (default=Off). If ON is selected, fan
can be set to Auto, Low, Med, or High.

Smart Recovery:

S

On or Off (default=On)

Applies to programmable operation only. Will start recovery 90

minutes prior to schedule change in both heating and cooling
mode. Refer to operational information for more detail.
English/Metric Display:

S _

F or _C, (default = _F)

CCUI

D

01

--

B