Bard Bayrd Furnace 403293A User Manual

Page 58

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

EXAMPLES USING SINGLE

APPLIANCE VENTING TABLES

Example 1; Single Draft-Hood-Equipped Appliance

Suppose that an installer has a 120,000 8tu/hr input

apptiafx:e with a 5 inch diameter draft hood outlet that
needs to be vented into a 10 foot high Type В vent
system. What size vent should be used assuming (a) a 5-
Ft lateral single-wall metal vent connector is used with

two 90° elbows, (b) a 5-Ft lateral single-wall metal vent
connector is used with three 90° elbows in the vent
system?

Solution

Table 2 should be used to solve this problem because
single-wall metal vent connectors are being used with a
Type В vent: Refer to Figure 4 of Typical Applications.

(a)

Read down the first column in Table 2 until the row
associated with a 10-Ft height and 5-Ft lateral is

found. Read across this row until a vent capacity
greater than 120,000 Btu/hr is located in the

shaded columns labeled "NAT Max" tor dratt-hood-

equipped appliances. In this case, a 5 inch
diameter vent has a capacity of 122,000 Btu/hr and
may be used for this ai^lication.

(b)

If three 90° elbows are used in the vent system,

then the maximum vent capacity listed in the tables

rTMJst be reduced by 10 percent (see Note 3). This
implies that the 5 inch diameter vent has an
adjusted capacity of only 110,000 Btu/hr. in this

case, the vent system must be increased to 6
inches in diameter. See calcutations below:

122,000

X

.90 * 110,000 for 5" Vent

From Table 2 - Select 6" Vent

186,000 X .90 =! 167,000; This is greater than the
required 120,000, therefore use a 6" Vent and

connector when three elbows are used.

Example 2: Single Fan-Assisted Appliance

Suppose an installer has an 80,000 Btu/hr input fan-
assisted ai:^liance that must be installed using 10 feet of
lateral connector attached to a 30-Ft high Type В vent.
Two 90° elbows are needed for the installation. Can a
single-wall metal vent connector be used for this
application?

Solution

Table 2 refers to the use of single-wall metal vent

connectors with Type 8 vent. In the first column find the

row associated with a 30-Ft height and a 10-Ft lateral.
Read across this row, looking at the "FAN Min" and "FAN
Max" columns, to find that a 3 inch diameter single-wall
metal connector vent is not recommended. Moving to

the next larger size sii^le wall connector (4") we find that

a 4 inch diameter single-wall metal connector has a
recommended minimum vent capacity of 91,000 Btu/hr
and a recommended maximum vent capacity of 144,000
Btu/hr. The 80,000 Btu/hr fan-assisted appliance is
outside this range, so we conclude that a single-wall
metal vent connector cannot be used to vent this
appliance using 10 feet of lateral for the connector.

However, we see that if the 80,000 Btu/hr input
appliance could be moved to within 5 feet of the vertical
vent, then a 4 inch single-wall metal connector could be
used to vent the appliance. Table 2 shows the
acceptable range of vent capacities for a 4 inch vent with
5 feet of lateral to be between 72,000 Btu/hr and
157.000 Btu/hr.

If the appliance cannot be moved closer to the vertical
vent, then Type В vent could be used as the connector
material. In this case .Table 1 shows that (or a 30-Ft high
vent with 10 feet of lateral, the acceptable range of vent
capacities for a 4 inch diameter vent attached to a fan-
assisted appliance are between 37,000 Btu/hr and

150.000 Btu/hr.

56

EXAMPLE 2

10’ Lateral ■

30

О

Fan Assisted Appriance
00,000 BTUH Input

Advertising