Installation – Desa VUL18 User Manual

Page 15

Advertising
background image

www.desatech.com

119426-01A

15

Pipe Cap Tee
Nipple Joint

INSTALLATION

Continued

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up. NPT

tap must be upstream from heater (see Figures 15

or 16, depending on your model).
IMPORTANT:

Install equipment shutoff valve

in an accessible location. The equipment shutoff

valve is for turning on or shutting off the gas to

the appliance.

Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.

Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged heater valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment trap in

supply line as shown in Figures 15 or 16, depend-

ing on your model. Locate sediment trap where it is

within reach for cleaning. Install in piping system

between fuel supply and heater. Locate sediment

trap where trapped matter is not likely to freeze.

A sediment trap traps moisture and contaminants.

This keeps them from going into heater controls. If

sediment trap is not installed or is installed wrong,

heater may not run properly.

CAUTION: Avoid damage to

regulator. Hold gas regulator

with wrench when connecting

it to gas piping and/or fittings

(Thermostatically-Controlled

Models Only).

CAUTION: Avoid damage to

gas control. Hold gas control

with wrench when connecting

it to gas piping and/or fittings

(Remote-Ready Models Only).

Figure 15 - Gas Connection

(Thermostatically-Controlled Models Only)

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories, page 42.

**Minimum inlet pressure for purpose of input

adjustment.

Figure 16 - Gas Connection (Remote-

Ready Models Only)

Gas
Control

Tee Cap Pipe
Joint

Nipple

3" Minimum

Gas
Regulator

PROPANE/LP
From External
Regulator
(11" W.C.**
to 14" W.C.
Pressure)

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

Approved Flexible
Gas Hose (if
allowed by local
codes)

Sediment Trap

NATURAL
From Gas
Meter
(5" W.C.**
to 10.5"
W.C.
Pressure)

3" Minimum

Sediment Trap

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

Approved Flexible
Gas Hose (if
allowed by local
codes)

PROPANE/LP

From External

Regulator

(11" W.C.**

to 14" W.C.

Pressure)

NATURAL

From Gas

Meter

(5" W.C.**

to 10.5"

W.C.

Pressure)