Dell 5600R OL HV-US User Manual

Page 43

Advertising
background image

43

Operation

|

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Set Date and Time

Set Month, Day, Year, Hours, Minutes, and Seconds

Date: mm/dd/yyyy

Time: hh:mm:ss

NOTE:

The date format is dependent on the

language selection.

NOTE:

Time is a 24-hour clock.

01/01/2009

12:00:00

Control Commands from Serial
Port

[Enabled] [Disabled]

If Enabled, control commands are accepted through
the serial port, USB ports, or option card.

If Disabled, configuration and load control
commands are restricted to LCD only.

Enabled

Output Voltage

[Auto-sensing]

Auto-sensing

[200V] [208V]

[220V] [230V] [240V]

Output Frequency

[50Hz] [60Hz] [Auto-sensing]

Auto-sensing

Overload Alarm Level

[10%] [20%] [30%]...[100%]

If 100%, the UPS issues an Output Overload alarm
at load > 100%.

NOTE:

Output Overload Level 1 by default is set to

100% and is configurable from 10% to 100% in 10%
increments through the LCD setting menu. This
feature allows customers to be alerted before the
UPS has reached its rated capacity limits.

100%

Automatic Start Delay

[Off] [0s] [1s] [2s]...[32767s]

See “Configuring Load Segments” on page 49.

LS1 0s

LS2 1s

Automatic on Battery Shutdown

[Off] [0s] [1s] [2s]...[32767s]

See “Configuring Load Segments” on page 49.

Off

Start on Battery

[Enabled] [Disabled]

NOTE:

Battery start is disabled from the factory and

remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. If this is set
by the user, it remains set.

Enabled

Advertising
This manual is related to the following products: