Troubleshooting

|

Table 16. Typical Alarms and Conditions (continued)

Alarm or Condition

Action

Possible Cause

Battery Test Failed

(Alarm 191)

Intermittent Alarm

A weak battery string was
detected during the last battery
test.

This is a warning notice. Dell recommends
that you replace the batteries soon.

Service Battery

(Alarm 149)

Continuous Alarm

A faulted battery string has
been detected and as a result,
the charger is disabled.

Contact your service representative.

Utility Not Present

(Alarm 59)

Intermittent Alarm

The utility level has fallen
below the Utility Not Present
threshold (typically <25 to
50V).

Transfer to battery if supporting load. Power
down if not supporting load.

Bypass Not Available

(Alarm 105)

The utility is outside of the
bypass limits defined in the
UPS.

Check the bypass settings. See “Settings” on
page 42.

Input AC Over Voltage

(Alarm 6)

Intermittent Alarm

The utility voltage exceeds the
maximum operating range.

The UPS transfers to Battery mode if
supporting load.

Input AC Under Voltage

(Alarm 7)

Intermittent Alarm

The utility voltage is below the
minimum operating range.

The UPS transfers to Battery mode if
supporting load.

Input Under/Over Frequency

(Alarm 8)

Intermittent Alarm

The utility frequency is out of
usable frequency range.

The UPS transfers to Battery mode if
supporting load.

Site Wiring Problem

(Alarm 194)

Continuous Alarm

An alarm triggers when the
difference between ground and
neutral voltage is >15V.

Have a qualified electrician correct the wiring
problem. If the UPS is not wired with a neutral
wire, Site Fault should be disabled in the
Settings menu (see page 42).

Remote Emergency Power
Off

(Alarm 12)

Continuous Alarm

The external contacts in the
rear of the UPS are configured
for REPO operation and they
have been activated.

The UPS de-energizes the load and enters
Standby mode. See “Installing Remote
Emergency Power-off” on page 25 for more
information.

Output Overload

(Alarm 25)

Continuous Alarm

The load level is at or has
exceeded the configurable
threshold limit for a Level 1
Overload condition.

The UPS can support the load indefinitely at
this load level.

The alarm clears when the load drops below
5% of the set point.