Dell 5600R OL HV-US User Manual

Page 45

Advertising
background image

45

Operation

|

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Synchronization Window

[Sync Disabled] [±0.5 Hz] [±1.0 Hz] [±1.5 Hz]
[±2.0 Hz] [±2.5 Hz] [±3.0 Hz]

If ±3.0 Hz, on inverter operation the inverter tries to
synchronize with the Bypass when the Bypass
frequency is not more than 3 Hz from the nominal
output frequency; otherwise, the inverter goes to
nominal frequency. On Bypass mode, the sync
window is always ±3 Hz.

NOTE:

In Sync Disabled state, if the Bypass

operation is allowed, the UPS synchronizes only
when it is operating on Bypass mode.

±

3.0 Hz

Unsynchronized Transfers

[Enabled] [Disabled]

If Enabled, unsynchronized transfers to the Bypass
are allowed.

If Disabled, unsynchronized transfers to the Bypass
are not allowed.

NOTE:

The Qualify Bypass setting may overrule the

Unsynchronized Transfers setting.

Enabled

External Battery Modules (EBMs)

[0] [1]

See “Configuring the UPS for an EBM” on page 52.

0

Charger

[Enabled] [Disabled]

If Enabled, batteries charge normally.

If Disabled, the battery charger is off.

Enabled

Battery Charge % to Restart

[0%] [10%] [20%] [30%]...[100%]

When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0%, the feature is disabled.

0%

Battery Low Alarm

[Immediate] [2 min] [3 min] [5 min]

If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.

3 min

Automatic Battery Tests

[Enabled] [Disabled]

See “Running Automatic Battery Tests” on page 53.

Enabled