Appendix  1  Statics,  Interference  Lightning  and  Surge  Protection  

This  product  adopts  TVS  plate  lightning  protection  technology  to  avoid  damage  caused  by  pulse  signal  that  is  below  
3000W,  like  instantaneous  lighting  stroke,  surging,  etc.  According  to  the  actual  outdoor  situation,  necessary  protection  
measures  must  be  taken,  besides  ensuring  the  electrical  safety.  

!

The  distance  between  signal  transmission  wires  and  High-­‐voltage  equipment  or  high-­‐voltage  cable  is  at  least  50m.  

!

Outdoor  wiring  should  better  be  routed  under  eaves  as  much  as  possible.  

!

In  the  open  field,  wiring  should  be  buried  underground  in  sealed  steel  pipe,  and  the  steel-­‐pipe  should  be  one-­‐point  
grounding.  Overhead  routing  method  is  forbidden.  

!

In   strong   thunderstorm   area   or   high   induction   voltage   areas   (such   as   high-­‐voltage   transformer   substation),   high  
power  lightning  protection  apparatus  and  lightning  conductor  are  necessary  to  be  added.  

!

The  design  of  lightning  protection  and  grounding  of  the  outdoor  devices  and  cables  should  be  considered  together  
with   the   lightning   protection   demand   of   buildings.   It   also   must   conform   to   the   related   national   standards   and  
industrial  standards.  

!

The  system  should  be  equipotential  grounded.  The  grounding  equipment  must  conform  to  the  demands  of  system  
anti-­‐jamming   and   electrical   safety   both   and   it   must   not   appear   short   circuit   or   mixed   circuit   with   the   zero  
conductor   of   strong   grid.   When   the   system   is   grounded   alone,   the   resistance   should   be   no   more   than   4Ω.   The  
sectional  area  of  the  grounding  cable  should  be  no  less  than  25mm2.  For  grounding  instructions,  please  refer  to  the  
Installation  Manual  of  Speed  Dome.  

 

Figure  A-­‐1  Lightning  &  Surge  Protection  

Grounding  for  Cement  Pole/Wall  Installation:  