Appendix  5  24VAC  Wire  Gauge  &  Transmission  Distance  

The  following  table  describes  the  recommended  max.  distance  adopted  for  the  certain  wire  gauge  when  the  loss  rate  of  
24VAC  voltage  is  less  than  10%.  For  the  AC  driven  device,  the  maximum  voltage  loss  rate  is  10%  allowable.  For  example,  
for  a  device  with  the  rating  power  of  80VA  which  is  installed  at  a  distance  of  35  feet  (10m)  away  from  the  transformer,  
then  0.8000mm  is  required  as  the  minimum  wire  gauge.  

0.8000  

1.000  

1.250  

2.000  

10  

283(86)  

451(137)  

716(218)  

1811(551)  

20  

141(42)  

225(68)  

358(109)  

905(275)  

30  

94(28)  

150(45)  

238(72)  

603(183)  

40  

70(21)  

112(34)  

179(54)  

452(137)  

50  

56(17)  

90(27)  

143(43)  

362(110)  

60  

47(14)  

75(22)  

119(36)  

301(91)  

70  

40(12)  

64(19)  

102(31)  

258(78)  

80  

35(10)  

56(17)  

89(27)  

226(68)  

90  

31(9)  

50(15)  

79(24)  

201(61)  

100  

28(8)  

45(13)  

71(21)  

181(55)  

110  

25(7)  

41(12)  

65(19)  

164(49)  

120  

23(7)  

37(11)  

59(17)  

150(45)  

130  

21(6)  

34(10)  

55(16)  

139(42)  

140  

20(6)  

32(9)  

51(15)  

129(39)  

150  

18(5)  

30(9)  

47(14)  

120(36)  

160  

17(5)  

28(8)  

44(13)  

113(34)  

170  

16(4)  

26(7)  

42(12)  

106(32)  

180  

15(4)  

25(7)  

39(11)  

100(30)  

190  

14(4)  

23(7)  

37(11)  

95(28)  

200  

14(4)  

22(6)  

35(10)  

90(27)  

 
 

Wire  Gauge    

(mm)  

Distance  

 (feet)  

 

Power  (va)  