Output characteristics – ADLINK cPCIS-ET1100 Series User Manual

Page 42

Advertising
background image

36

•

Power Supply Unit

•

Dielectric Withstand: Meets IEC950 regulation

•

EMI: Meets EN55022 / FCC Class A

•

Hold-up Time: 5mS after power fail signal

•

Remote ON/OFF: Available at [INH#] & [EN#] pins

•

Power Fail Signal: Available at [FAL#] pin

•

Status LED: <Green> means valid input voltage; <Amber> means a
critical fault.

•

Thermal Protection (OTP): Installed NTC and thermostat for thermal
sensor at [DEG#] pin

•

Power OK: Installed at all outputs

•

Leakage Current: Typ. 0.5mA

Output Characteristics

Output Current (A)

Output

Voltage

MIN.

MAX.

TYP.

PEAK.

5V

MAIN +VO1

@ ★ # ≡ ⊙

2.0 33.0 25.0

–

3.3V

AUX. +VO2

▲ @ ★ # ≡ ⊙

0 33 18 –

12V

AUX. +VO3

▲ ≡ # ⊙ ★ @

0 5.5 5.5 6

-12V

AUX. –VO4

● ⊙ ★ ■ =

0 1 0.5

1.5

Symbol: "★" OVP built-in; "@" Adjustable; "#" Remote sensing;

"≡" 3rd-wire Load Sharing; "=" Droop Current Sharing;
"⊙" Installed with Or-ing diode; "▲" Magnetic Amplifier;
"●" Installed with Post-regulator; "■" Common Choke.


Remarks: Peak load sustainable for less than 60sec. with duty cycle <10%.

Max. load is the continuous operating load of each rail. Max. load
of each rail cannot be drawn from all outputs at the same time.


Advertising