2 isolated digital output, Figure 2-2: common ground connection – ADLINK MXC-4000 Series User Manual

Page 26

Advertising
background image

16

System Description

Matrix MXC-4000 Series

User’s Manual

2.3.2

Isolated digital Output

Common ground connection of isolated digital output and common
power connection of isolated digital output are shown.

When isolated digital output enters an “ON” state, sink current is
conducted through the transistors. When an “OFF” state is
entered, there is no current through the transistors.

Note:

When the load is of an “inductance nature” such as a

relay, coil or motor, the VDD pin must be connected to an

external power source, with the extra connection utilized

for the ‘fly-wheel diode’ to form a current-release closed

loop, by which the transistors are protected from high

reverse voltage generated by the inductance load when

the output is switched from “ON” to “OFF”.

Figure 2-2: Common Ground Connection