Menu option found in installer display menu of each

individual boiler. Press menu and enter buttons on user

interface simultaneously for 5 second to enter Installer

menu. See fi gure 5.

One boiler is MANAGING (Boiler Address: 1) and all other

boilers work as dependent (address 2..16). Each boiler

should have its unique address. Manually program each

boiler's address.

boiler_ address

Parameter Value

Boiler Operation

Function of

system sensor

input

0 (default)

No cascade boiler

No function

1

1st boiler (MANAGING)

System sen-

sor

2

2nd boiler (dependent)

No function

3

3rd boiler (dependent)

No function

4

4th boiler (dependent)

No function

16

16th boiler (dependent) No function

Once boiler is defi ned as dependent (addresses 2..16) display will show boiler supply temperature and boiler status.
Use managing display (Boiler Address = 1) and managing boiler controls to determine demands for heat or DHW and

show system temperature.

Menu option:

MULTIPLE BOILER GUIDE

Figure 5 - User Interface