Multiple boiler guide – Dunkirk Helix VLT Vertical Laser Tube, Wall Hung Modulating Condensing Boiler User Manual

Page 9

Advertising
background image

9

Specifi c Parameters

Level

(Default) Value

Range

°C

°F

°C

°F

Permit Boiler Emergency Mode

[-]

1: User

yes

yes/no

Cascade CH Setpoint

[ºC/ºF]

1: User

80

160

40..93

104..200

Boiler Address

[-]

2: Installer

0

0..15

0..15

Cascade Emergency Setpoint

[ºC/ºF]

2: Installer

45

113

20..65

68..149

Start Delay Time

[min]

2: Installer

3

1..15

Stop Delay Time

[min]

2: Installer

3

1..15

Start Boiler Diff

[ºC/ºF]

2: Installer

5

9

0..20

0..36

Stop Boiler Diff

[ºC/ºF]

2: Installer

2

18

0..20

0..36

Calculated setpoint Max offset down

[ºC/ºF]

2: Installer

4

36

0..20

0..36

Calculated setpoint Max offset up

[ºC/ºF]

2: Installer

10

18

0..20

0..36

Start Modulation Delay Factor

[-]

2: Installer

5

0=disabled

1..60

Next Boiler Start Rate

[%]

2: Installer

80

10..100

Next Boiler Stop Rate

[%]

2: Installer

30

10..100

Rotation Interval

[days]

2: Installer

1

0..30

0=disabled

Boilers for DHW

[-]

2: Installer

all

All,1..16

Not

available

System Pump - Post Pump Time

[sec]

2: Installer

30 seconds

1…90

MULTIPLE BOILER GUIDE