MAINTENANCE

fault

codes Description

Cause

Solution

526

Evaporation/condensation

temperature sensor failure

The sensor is defective or is not

correctly connected to the main

PCB.

Check the sensor’s connections.

Check that the position and the operation of the sensor are correct.

Check the sensor’s resistance.

528

Plate to plate heat exchanger

temperature sensor failure

532

The brine circuit flow is too

low (<500 l/h) .

Blocking failure if produced

more than 3 times.

The brine circuit flow is too low.

Force the pump and check the flow.

Adjust the water flow by changing the speed of the pump or opening

the hydraulic module control valve.

There is a lack of water.

Check the brine circuit. If the valve leaks, replace the valve, add water

and degas the circuit.

Anti-silt filter missing or clogged

in the brine water circuit’s

backflow.

Install an anti-silt filter.

Clean the anti-silt filter.

The circuit was not properly bled. Activate the bleeding function and top up the glycol water if necessary.

The expansion vessel is

defective.

Check the pressure of the expansion vessel.Reinflate the expansion

vessel.

Replace the expansion vessel.

534

The output temperature of the

circuit brine is too high

(> 57°C).

Non-blocking failure.

The sensor is defective or is not

correctly connected to the main

PCB.

Check the sensor’s connections. Check that the position and the

operation of the sensor are correct.

Check the sensor’s resistance.

Faulty indication of water flow.

Check that there is no water flow by closing a valve in the brine circuit.

The expansion vessel is

defective.

Check the pressure of the expansion vessel.

Reinflate the expansion vessel.

Replace the expansion vessel.

Anti-silt filter missing or clogged

in the brine water circuit’s

backflow.

Install an anti-silt filter.

Clean the anti-silt filter.

Air in the brine water circuit

Drain the brine water circuit

536

The compressor discharge

temperature is too high

(> 105°C).

Blocking failure if produced

more than 3 times.

There is an excess or a lack of

refrigerant.

Measure the air and water’s ΔT. If it is very low (<2K), lack of fluid

may be the cause (loss of heat output). Measure the real overheating

(must be <7K in heating mode). Measure the electrical current with an

ammeter. If the current is below 4.5 amps, the cause may be a lack of

fluid.

Check the pressure with a monometer.

Check that there are no leaks, repair them if necessary.

Adjust the amount of refrigerant.

The temperature sensor is

defective or is not correctly

connected to the main PCB.

Check the connections from the sensor to the discharge. Check that the

position and the operation of the sensor are correct. Check the sensor’s

resistance.

The water flow sensor is

defective.

Check absence of water flow by forcing the pump. Consult the

"Adjusting the HP flow circuit” chapter.

Pre-expansion in the liquid line

(load loss)

Check the appearance of the condenser output tubes leading to the

evaporator (do not pinch).

The electronic expansion valve is

defective.

Check that the motor is correctly clipped to the regulator.

Check that the electronic is working correctly, if this is not the case:

Check the winding resistance.

Replace the motor.

Replace the electronic expansion valve, check that there are no leaks.

Scale on the plate to plate

exchanger.

Clean the heat exchanger plates.

The heating outlet and return

temperature sensors are

defective.

Check the sensor connections.

Check that the sensor position and operation are correct.

Check the sensor resistance.

The air temperature is too high in

cooling mode.

Check the agreement between the outside sensor and heat pump air

inlet temperature sensor.

Check that the heat pump air inlet temperature sensor is working

properly.

In de-icing mode, the de-icing

sensor is defective or misplaced.

Check the sensor connections.

Check that the sensor position and operation are correct.

Check the sensor resistance.